INSP-Final | 5/31/2019 | 5/31/2019 | 5/31/2019 | P | DONE |
Troy Cobbley
|
|
|
Permit finaled.
Phone #: ###-#### Inspection requested via web by jeremiah robison
|
DOC - Permit Finaled | | | 5/31/2019 | | DONE |
|
|
|
as per Troy Cobbley-doc final-final inspection passed
|
INSP-Sprinkler Rough-in | 5/22/2019 | 5/23/2019 | 5/23/2019 | A | PASS |
Troy Cobbley
|
|
|
hangers added, 4 Heads changed that where painted and heads swapped out to standard response to match. The piping is ok for cover. Phone #: ###-#### Inspection requested via web by jeremiah robison
|
INSP-Sprinkler Rough-in | 5/20/2019 | 5/20/2019 | 5/20/2019 | P | PART |
Troy Cobbley
|
|
|
Sprinkler spacing appears ok for State Fires scope of work but I noted painted heads, missing hangers. It also appears that the existing light fixtures/architectual features are blocking the pendant heads. This issues needs to be addressed now, which will require a plan modification, if it is with-in the building permit scope of work. If outside of the scope of work then the Boise Fire Dept will follow up for corrections.
Phone #: ###-#### Inspection requested via web by jeremiah robison
|
Staff review | 5/17/2019 | 5/17/2019 | 5/17/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 5/17/2019 | | 5/17/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Miscellaneous action | | | 5/17/2019 | | DONE |
|
|
|
emailed Shelley the permit #- Ron J brought the paper plans in
|
Permit Ready to Issue | | | 5/17/2019 | | DONE |
|
|
|
|
Issue and Courier | | | 5/17/2019 | | DONE |
|
|
|
emailed Shelley and called Ron J (left message on Ron's phone) to come get since Shelley is on vacation
|
Application received | | | 5/17/2019 | | |
|
|
|
|