INSP-Final | 9/6/2019 | 9/9/2019 | 9/9/2019 | A | DONE |
Troy Cobbley
|
|
|
Permit finaled
Thank you Phone #: ###-#### Inspection requested via web by jeremiah robison
|
DOC - Permit Finaled | | | 9/9/2019 | | DONE |
|
|
|
Per Troy C and final inspection
|
INSP-Final | 9/5/2019 | 9/6/2019 | 9/6/2019 | A | FAIL |
Troy Cobbley
|
|
|
Two pendant heads are blocked in the southeast lower ceiling/room by surface mounted lights. One pendant in the high is still covered with tape. All other items appear okThank you have a nice day Phone #: ###-#### Inspection requested via web by jeremiah robison
|
INSP-Sprinkler Rough-in/Hydro | 7/16/2019 | 7/17/2019 | 7/17/2019 | P | PASS |
Troy Cobbley
|
|
|
Overhead hydro test passed. Overhead rough-in passed. Piping can be covered.
Contact: Leon Taylor Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
INSP-Sprinkler Rough-in/Hydro | 7/16/2019 | 7/16/2019 | 7/16/2019 | P | CANC |
Troy Cobbley
|
|
|
Conact: Leon Taylor Phone #: ###-#### >> Inspection requested via web by Hunter Fillmore Inspection cancelled from web by: Hunter Fillmore
|
INSP-Sprinkler Rough-in/Hydro | 7/16/2019 | 7/17/2019 | 7/16/2019 | P | FAIL |
Troy Cobbley
|
|
|
Failed hydro-did not maintain pressure. Dropped 20 psi in 2 hours. Not ready for rough in, no small docs or stamped prints on site.
Contact: Leon Taylor Phone #: ###-#### >> Inspection requested via web by Hunter Fillmore
|
Miscellaneous action | | | 7/12/2019 | | DONE |
|
|
|
sent Shelley an email-the contractor was supposed to come pick up the permit here 7/11/19. I told her if he wasn't here by the end of the day 7/12/18 I'd put it in the inner office mail to go back to NACFR
|
Miscellaneous action | | | 7/10/2019 | | DONE |
|
|
|
mailing found plans andbrought them to Candy's desk-contractor will be in to get them-per Shelley at NACFR ok for pickup here at the city
|
Staff review | 7/8/2019 | 7/8/2019 | 7/9/2019 | | PASS |
Mark Stumbaugh
|
|
|
resubmittal
Total review time for both submittals 2hr - 1hr ea.
|
Plan assigned to (Stumbaugh) | 7/8/2019 | | 7/9/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/9/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 7/9/2019 | | DONE |
|
|
|
|
Issue and Courier | | | 7/9/2019 | | DONE |
|
|
|
2 hr plan review time for both resubmittals-emailed Shelley that the permit was in the inner office mail
|
Staff review | 6/26/2019 | 6/26/2019 | 7/8/2019 | | FAIL |
Mark Stumbaugh
|
|
|
Failed pre-screen - missing data sheets
|
Plan assigned to (Stumbaugh) | 6/26/2019 | | 7/8/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Plan resubmittals received | | | 7/8/2019 | | DONE |
|
|
|
resubmittal recieved 4 sets of app, 4 correction details, 4 calcs & 4 sheets of FP-1-assigned to MAS
|
Application received | | | 6/26/2019 | | |
|
|
|
|