Telephone call | | | 3/1/2002 | | DONE |
|
|
|
requested 2/22/02 and 2/27/02
|
PLM-Aging Inspection | 12/24/2001 | 12/26/2001 | 12/26/2001 | A | PASS |
Bill VanDegrift
|
|
|
Scheduled by Inspector: 309 On 12/24/2001 7:48:47 AM the final for the express store is ok 12/26/2001 8:39:28 AM
|
DOC - Permit Finaled | 12/26/2001 | 12/26/2001 | 12/26/2001 | A | PASS |
Bill VanDegrift
|
|
|
Finaled by inspector at 12/26/2001 8:39:30 AM
|
PLM-Aging Inspection | 12/24/2001 | 12/24/2001 | 12/24/2001 | | CANC |
Lee Rice
|
|
|
|
PLM-Aging Inspection | 10/23/2001 | 10/23/2001 | 10/23/2001 | | NR |
Bill VanDegrift
|
|
|
|
CHANGE STATUS TO (I) | | | 10/8/2001 | | DONE |
|
|
|
|
Final | 8/23/2001 | 8/23/2001 | 8/23/2001 | P | PART |
Bill VanDegrift
|
|
|
Added by Inspector: 330 On 8/23/2001 4:22:56 PM most of the cross connection protection is taken care of, temp occ ok
|
Final | 8/17/2001 | 8/20/2001 | 8/20/2001 | P | FAIL |
Bill VanDegrift
|
|
|
Scheduled by Inspector: 330 On 8/17/2001 3:19:42 PM many corrections left notice with plumber 8/21/2001 3:35:32 PM
|
Final | 8/16/2001 | 8/17/2001 | 8/17/2001 | P | CANC |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 08/16/2001 at 14:20:49. Contact: ###-####.
|
Plumbing Rough-in | 7/3/2001 | 7/3/2001 | 7/3/2001 | A | PASS |
Lee Rice
|
|
|
Scheduled by a contractor via Hello! on 07/03/2001 at 07:24:49. Contact: ###-####. r/i ok on pharmacy and phot shop. 7/3/2001 11:07:56 AM
|
Plumbing Rough-in | 6/14/2001 | 6/14/2001 | 6/14/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 06/14/2001 at 08:04:39. Contact: ###-####. public restrooms ri ok 6/14/2001 2:49:18 PM
|
Plumbing Rough-in | 6/6/2001 | 6/6/2001 | 6/6/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 06/06/2001 at 07:37:20. Contact: ###-####. deli vents, 6/6/2001 3:37:39 PM interceptors and sewers 6/6/2001 3:56:45 PM
|
Plumbing Rough-in | 6/6/2001 | 6/6/2001 | 6/6/2001 | A | PART |
Bill VanDegrift
|
|
|
Added by Inspector: 330 On 6/6/2001 11:23:30 AM water in walls in deli area test ok
|
Other | 6/5/2001 | 6/5/2001 | 6/5/2001 | P | CANC |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 06/05/2001 at 07:13:06. Contact: ###-####.
|
Plumbing Rough-in | 5/30/2001 | 5/30/2001 | 5/30/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 05/30/2001 at 08:25:23. Contact: ###-####. vent i produce area 5/30/2001 2:54:42 PM
|
Plumbing Rough-in | 5/23/2001 | 5/23/2001 | 5/23/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 05/23/2001 at 07:34:38. Contact: ###-####. test on that leaky section from last time ok , combo w&v vents ok, water in meat 5/23/2001 1:57:21 PM and fish , misc. vents in back service area 5/23/2001 1:58:14 PM
|
Plumbing Rough-in | 5/17/2001 | 5/17/2001 | 5/17/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 05/17/2001 at 07:45:11. Contact: ###-####. backarea plumbing ok except 1 section at meat counter backwall with leak in vent. 5/17/2001 2:30:39 PM
|
Plumbing Rough-in | 5/16/2001 | 5/16/2001 | 5/16/2001 | P | NR |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 05/16/2001 at 07:58:36. Contact: ###-####.
|
Groundwork | 4/6/2001 | 4/9/2001 | 4/9/2001 | A | NR |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 04/06/2001 at 14:21:57. Contact: ###-####.
|
Groundwork | 4/9/2001 | 4/9/2001 | 4/9/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 04/09/2001 at 08:00:30. Contact: ###-####. comb w&v north wall 4/9/2001 3:30:37 PM
|
Groundwork | 4/6/2001 | 4/6/2001 | 4/6/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 04/06/2001 at 09:10:11. Contact: ###-####.
|
Groundwork | 4/4/2001 | 4/4/2001 | 4/4/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 04/04/2001 at 07:45:04. Contact: ###-####.
|
Groundwork | 3/28/2001 | 3/29/2001 | 3/29/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 03/28/2001 at 15:57:22. Contact: ###-####.
|
Groundwork | 3/27/2001 | 3/27/2001 | 3/27/2001 | P | PART |
Gerry Varner
|
|
|
Scheduled by a contractor via Hello! on 03/27/2001 at 08:51:51. Contact: ###-####.
|
Groundwork | 3/23/2001 | 3/23/2001 | 3/23/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 03/23/2001 at 08:30:58. Contact: ###-####.
|
Groundwork | 3/21/2001 | 3/21/2001 | 3/21/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 03/21/2001 at 09:27:18. Contact: ###-####. meat and fish area 3/21/2001 2:55:46 PM
|
Groundwork | 3/20/2001 | 3/20/2001 | 3/20/2001 | A | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 03/20/2001 at 07:08:24. Contact: ###-####.
|
Groundwork | 3/19/2001 | 3/19/2001 | 3/19/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 03/19/2001 at 11:05:41. Contact: ###-####.
|
Groundwork | 3/15/2001 | 3/16/2001 | 3/16/2001 | A | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 03/15/2001 at 09:40:44. Contact: ###-####. deli area case drains gw ok 3/16/2001 11:13:06 AM
|
Groundwork | 3/14/2001 | 3/15/2001 | 3/15/2001 | A | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 03/14/2001 at 16:19:07. Contact: ###-####. bakery area grease waste and water service stubin ok 3/15/2001 9:12:06 AM
|
Groundwork | 3/13/2001 | 3/13/2001 | 3/13/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 03/13/2001 at 09:49:19. Contact: ###-####. upper end of deep main from ne to se 3/13/2001 4:07:35 PM
|
Groundwork | 3/8/2001 | 3/8/2001 | 3/8/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 03/08/2001 at 09:11:35. Contact: ###-####. 4" s.s. from ne corner south 100' 3/8/2001 3:26:06 PM
|
Groundwork | 3/5/2001 | 3/6/2001 | 3/6/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 03/05/2001 at 15:44:52. Contact: ###-####. this is the third time ive entered this inspection and the computor keeps sending it back to me 3/7/2001 8:08:45 AM
|
Groundwork | 3/6/2001 | 3/6/2001 | 3/6/2001 | P | FAIL |
Bill VanDegrift
|
|
|
Added by Inspector: 330 On 3/6/2001 2:56:58 PM southern east/west waste and grease lines have backgraded areas
|
Groundwork | 2/28/2001 | 2/28/2001 | 2/28/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 02/28/2001 at 10:50:57. Contact: ###-####. main deep east/west to east end and deep north south main to south end ok 2/28/2001 4:23:37 PM
|
Groundwork | 2/26/2001 | 2/26/2001 | 2/26/2001 | P | PART |
Bill VanDegrift
|
|
|
Scheduled by a contractor via Hello! on 02/26/2001 at 08:19:44. Contact: ###-####. waste from low end to half way thru building east and south mains to 2nd grease line co 2/26/2001 2:02:41 PM
|
Application received | | | 2/22/2001 | | |
|
|
|
|
Issue & PRINT permit | | | 2/22/2001 | | DONE |
|
|
|
|