Final | 10/13/2003 | 10/13/2003 | 10/13/2003 | P | PASS |
Jim Johnson
|
|
|
|
DOC - Permit Finaled | 10/13/2003 | 10/13/2003 | 10/13/2003 | P | PASS |
Jim Johnson
|
|
|
Finaled by inspector at 10/13/2003 2:35:46 PM
|
Final | 10/9/2003 | 10/10/2003 | 10/10/2003 | A | FAIL |
Jim Johnson
|
|
|
jennette; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie u.p.c. 601.2.1 need to provide approved signage on hose bibb on sprinkler r.p and on hose bibb on west side of building need to anchor hose bibb,s on building need to caulk up stair,s lav and water closet 10/10/2003 10:47:24 AM
|
Plumbing Rough-in | 8/1/2003 | 8/1/2003 | 8/1/2003 | P | PASS |
Jim Johnson
|
|
|
Scheduled by a contractor via Hello! on 8/1/2003 at 7:39:18 AM. Contact: ###-####.
|
Plumbing Rough-in | 7/31/2003 | 7/31/2003 | 7/31/2003 | P | FAIL |
Jim Johnson
|
|
|
need to support abs every 4 feet need to fix leak in 1 1/2 coupling in over head change upside down san tee in crawl for floor drain need to repipe 3 inch drain line to powder room bath so it is not subject to strain or stress talked to plumber on job will recall when ready 7/31/2003 5:33:52 PM
|
Application received | | | 7/31/2003 | | |
|
|
|
|
Issue & PRINT permit | | | 7/31/2003 | | DONE |
|
|
|
|