Third Notice PLM | 10/6/2003 | 10/6/2003 | 4/7/2004 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice PLM | 9/24/2003 | 9/24/2003 | 10/6/2003 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 8/28/2003 | 9/24/2003 | | DONE |
|
|
|
|
DOC - Permit Finaled | 8/28/2003 | 8/28/2003 | 8/28/2003 | P | PASS |
Jim Johnson
|
|
|
Finaled by inspector at 8/28/2003 2:51:10 PM
|
Sprinkler (Final) | 8/28/2003 | 8/28/2003 | 8/28/2003 | P | PASS |
Jim Johnson
|
|
|
|
Sprinkler (Final) | 8/26/2003 | 8/27/2003 | 8/27/2003 | A | PART |
Jim Johnson
|
|
|
tie in ok ok to cover need to have double check tested and certified contractor to recall when ready 8/27/2003 1:23:25 PM
|
Sprinkler (Final) | 8/25/2003 | 8/26/2003 | 8/26/2003 | A | FAIL |
Jim Johnson
|
|
|
###-#### kyle need to use listed p.v.c piping for potable water system to backflow device need two union,s for under ground installation on double check need test pluges for test ports on double check and have tested and certified talked to sprinkler foreman on job site 8/26/2003 4:32:16 PM
|
Issue PAID IN FULL permit | | | 8/25/2003 | | DONE |
|
|
|
|
Application received | | | 8/25/2003 | | |
|
|
|
|