Third Notice PLM | 5/4/2005 | 5/4/2005 | 6/23/2005 | | DONE |
|
|
|
This permit finaled on the web by Roger Patterson
|
Second Notice PLM | 4/18/2005 | 4/18/2005 | 5/4/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice Sent | | 3/14/2005 | 4/18/2005 | | DONE |
|
|
|
|
Water and/or Sewer | 3/14/2005 | 3/15/2005 | 3/15/2005 | A | PASS |
Jim Johnson
|
|
|
people their all day today. Internet Inspection Request from: Roger Patterson
|
DOC - Permit Finaled | 3/14/2005 | 3/14/2005 | 3/14/2005 | P | PASS |
Jim Johnson
|
|
|
Finaled by inspector at 3/14/2005 1:58:44 PM
|
Plumbing Rough-in | 1/27/2005 | 1/27/2005 | 1/27/2005 | P | NR |
Jim Johnson
|
|
|
Contact Mile with questions.; Phone #: ###-#### Internet Inspection Request from: Roger Patterson
|
Water and/or Sewer | 1/27/2005 | 1/27/2005 | 1/27/2005 | P | CANC |
Jim Johnson
|
|
|
Thanks Jim Internet Inspection Request from: Roger Patterson
|
Groundwork | 1/27/2005 | 1/27/2005 | 1/27/2005 | P | PASS |
Jim Johnson
|
|
|
|
Water and/or Sewer | 1/25/2005 | 1/26/2005 | 1/26/2005 | A | PART |
Jim Johnson
|
|
|
Mile will be at job wed. A.M.-needs to have test pulled by 10:30 so they can start cooking. thank you. Internet Inspection Request from: Roger Patterson under slab D.W.V. test ok need to use approved material for under slab water installation. need to pipe sink,s in kitchen area to floor sink separate. provide a thermal expansion tank on water heater and pipe t&p drain to approved location. will need to provide hot water limitation for public lavatories to 120 degrees 1/26/2005 1:59:21 PM
|
Application received | | | 1/21/2005 | | |
|
|
|
This permit was created on the web by Roger Patterson
|