Second Notice PLM | 7/23/2007 | 7/23/2007 | 8/16/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 2/9/2007 | 2/9/2007 | 7/23/2007 | | DONE |
Jim Johnson
|
|
|
|
Final | 2/8/2007 | 2/9/2007 | 2/9/2007 | A | PASS |
Jim Johnson
|
|
|
Phone #: ###-####
|
Final | 2/6/2007 | 2/7/2007 | 2/7/2007 | P | PART |
Jim Johnson
|
|
|
Phone #: ###-#### need to finish rest room in laundry area need to correct piping on ice machine in vending area,s on all floor,s need approved signage on non potable water out let,s in pool mech. room need identification tag,s on RP in kit. area over mop sink plumber changing PVB on hose reel in kit area to RP OKED TEMP
|
Final | 1/25/2007 | 1/29/2007 | 1/29/2007 | A | PART |
Jim Johnson
|
|
|
2nd and 3rd floors Phone #: ###-#### first and second floor room,s ok
|
Final | 1/22/2007 | 1/23/2007 | 1/23/2007 | P | PART |
Eric Strole
|
|
|
mechanical room Phone #: ###-####-mech room ok to insulate, need tempered water on hand sinks in kitchen area, booster pump in mech room is coming out, 3rd & 4yh flr rooms ok.
|
Final | 1/15/2007 | 1/16/2007 | 1/16/2007 | A | PART |
Jim Johnson
|
|
|
This inspection if for the 3rd and 4th floors. any questions, call ###-#### need bee hive strainer,s in floor sink,s need ice machine,s installed need to correct leak under sink in unit 412
|
PLM-Aging Inspection | 11/28/2006 | 11/28/2006 | 11/28/2006 | | PASS |
Jim Johnson
|
|
|
project under construction
|
PLM-Aging Inspection | 9/25/2006 | 9/25/2006 | 9/25/2006 | | PASS |
Jim Johnson
|
|
|
project under construction
|
Plumbing Rough-in | 7/21/2006 | 7/24/2006 | 7/24/2006 | A | PART |
Daryl Spivey
|
|
|
Water Mains ; Phone #: ###-#### Internet Inspection Request from: Brent Lacy Water lines all tested ok.... ds
|
Roof Drains | 7/11/2006 | 7/12/2006 | 7/12/2006 | A | PART |
Jim Johnson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brent Lacy storm drain on south west side test ok
|
Plumbing Rough-in | 7/7/2006 | 7/10/2006 | 7/10/2006 | A | PART |
Jim Johnson
|
|
|
Ready for inspection ; Phone #: ###-#### Internet Inspection Request from: Brent Lacy roof and overflow drain and vent,s in pool area test ok
|
Roof Drains | 6/28/2006 | 6/28/2006 | 6/28/2006 | P | PART |
Lee Rice
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brent Lacy
|
Plumbing Rough-in | 6/5/2006 | 6/6/2006 | 6/6/2006 | P | PART |
Jim Johnson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Brent Lacy main water lines hot and cold on third floor test ok DWV and water in lobby area public rest rooms and kit. area test ok
|
Roof Drains | 5/10/2006 | 5/11/2006 | 5/11/2006 | A | PASS |
Jim Johnson
|
|
|
Please schedule for around 9 am if possible. THANK YOU:); Phone #: ###-#### Internet Inspection Request from: Brent Lacy roof and overflow drains in lobby area test ok
|
Plumbing Rough-in | 5/4/2006 | 5/5/2006 | 5/5/2006 | A | PART |
Jim Johnson
|
|
|
at 9:00am if possible:); Phone #: ###-#### Internet Inspection Request from: Brent Lacy correction on leak,s in DWV on first and second floor,s south-east wing have been made and test ok
|
Plumbing Rough-in | 5/2/2006 | 5/3/2006 | 5/3/2006 | A | PART |
Jim Johnson
|
|
|
If possible we need the inspection around 10am or after. Thank you:); Phone #: ###-#### Internet Inspection Request from: Brent Lacy need to correct some leak,s in dwv on second and first floor and retest on south east wing contractor to call when ready
|
Plumbing Rough-in | 5/1/2006 | 5/1/2006 | 5/1/2006 | A | PART |
Jim Johnson
|
|
|
Ready for inspection ; Phone #: ###-#### Internet Inspection Request from: Brent Lacy water for ice mach. and wall hydrant,s test ok DWV on south-east wing end rooms only first and second floor test ok
|
Roof Drains | 5/1/2006 | 5/1/2006 | 5/1/2006 | A | PART |
Jim Johnson
|
|
|
Ready for inspection; Phone #: ###-#### Internet Inspection Request from: Brent Lacy roof and overflow drains on north west wing test ok
|
Plumbing Rough-in | 4/25/2006 | 4/26/2006 | 4/26/2006 | P | PART |
Jim Johnson
|
|
|
If possible, schedule around 2pm. Thank you:); Phone #: ###-#### Internet Inspection Request from: Brent Lacy water and DWV for 1st and 2nd floor on north west wing test ok
|
Plumbing Rough-in | 4/20/2006 | 4/21/2006 | 4/21/2006 | A | PART |
Jim Johnson
|
|
|
Early AM if possible. Thanks:); Phone #: ###-#### Internet Inspection Request from: Brent Lacy water on first and second floor,s test ok roof drains on south east side test ok need to correct two leaks on two over flow drain,s the other two on south east wing test ok
|
Plumbing Rough-in | 4/18/2006 | 4/19/2006 | 4/19/2006 | P | PART |
Jim Johnson
|
|
|
If possible, please schedule at 2pm. Thank you:); Phone #: ###-#### Internet Inspection Request from: Brent Lacy DWV on fourth and third floor of north west wing test ok
|
Plumbing Rough-in | 4/12/2006 | 4/13/2006 | 4/13/2006 | P | PART |
Jim Johnson
|
|
|
If possible, schedule inspection around 1:30pm; Phone #: ###-#### Internet Inspection Request from: Brent Lacy water and DWV on 4thand 3rd floor for south-east wing test ok water only on 4th and 3rd floor for north -west wing test ok
|
PLM-Aging Inspection | 3/22/2006 | 3/22/2006 | 3/22/2006 | | PASS |
Jim Johnson
|
|
|
still under construction
|
Roof Drains | 1/19/2006 | 1/20/2006 | 1/20/2006 | P | PASS |
Jim Johnson
|
|
|
If possible an inspection around 1 or 2pm would be perfect. Thanks.; Phone #: ###-#### Internet Inspection Request from: Brent Lacy
|
Groundwork | 12/12/2005 | 12/13/2005 | 12/13/2005 | P | PASS |
Jim Johnson
|
|
|
Ground work for pool area. ready at 2:00 PM ; Phone #: ###-#### Internet Inspection Request from: Brent Lacy
|
PLM-Aging Inspection | 11/16/2005 | 11/16/2005 | 11/16/2005 | | PASS |
Jim Johnson
|
|
|
project still under construction
|
Roof Drains | 9/15/2005 | 9/16/2005 | 9/16/2005 | A | PART |
Jim Johnson
|
|
|
Ready fisrt thing AM. ; Phone #: ###-#### Internet Inspection Request from: Brent Lacy storm drains on south west wing test ok ok to cover
|
Roof Drains | 9/13/2005 | 9/13/2005 | 9/13/2005 | P | PART |
Jim Johnson
|
|
|
Will be ready at 2:30. Thank You! Internet Inspection Request from: Brent Lacy roof drain,s on east side of north wing test ok
|
Roof Drains | 8/30/2005 | 8/30/2005 | 8/30/2005 | P | PART |
Jim Johnson
|
|
|
Ready @ 2:00 PM; Phone #: ###-#### Internet Inspection Request from: Brent Lacy roof draines on north east side of building test ok
|
Roof Drains | 8/25/2005 | 8/26/2005 | 8/26/2005 | A | PASS |
Daryl Spivey
|
|
|
Dan Furhman - Ready First Thing AM. Exterior Roof Drain Line. Internet Inspection Request from: Brent Lacy west end tie in to site drainage ok. ds
|
Groundwork | 8/19/2005 | 8/22/2005 | 8/22/2005 | A | PASS |
Jim Johnson
|
|
|
Ready by 8:30 AM Internet Inspection Request from: Brent Lacy
|
Groundwork | 8/12/2005 | 8/15/2005 | 8/15/2005 | A | PASS |
Jim Johnson
|
|
|
Ready at 11:00 AM Internet Inspection Request from: Brent Lacy
|
Other | 8/9/2005 | 8/11/2005 | 8/11/2005 | A | CANC |
Gary Ziegler
|
|
|
job conf. 900 am on site.
|
Groundwork | 7/29/2005 | 8/1/2005 | 8/1/2005 | P | PART |
Jim Johnson
|
|
|
Scheduled by a contractor via Hello! on 7/29/2005 at 2:29:31 PM. Contact: ###-####. south wing ground work ok
|
Groundwork | 7/20/2005 | 7/21/2005 | 7/21/2005 | A | PART |
Jim Johnson
|
|
|
Scheduled by a contractor via Hello! on 7/20/2005 at 2:31:49 PM. Contact: ###-####.
|
Plumbing Rough-in | 7/18/2005 | 7/19/2005 | 7/19/2005 | A | PART |
Jim Johnson
|
|
|
Scheduled by a contractor via Hello! on 7/18/2005 at 1:59:55 PM. Contact: ###-####. ground work on north wing test ok
|
Groundwork | 7/12/2005 | 7/13/2005 | 7/13/2005 | A | PART |
Jim Johnson
|
|
|
Will be ready @ 10:00 AM ; Phone #: ###-#### Internet Inspection Request from: Brent Lacy kitchen area and grease trap test ok
|
Groundwork | 7/7/2005 | 7/7/2005 | 7/7/2005 | P | PART |
Jim Johnson
|
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore sewer trunk line on south wing test ok
|
Groundwork | 6/28/2005 | 6/29/2005 | 6/29/2005 | P | PART |
Jim Johnson
|
|
|
partial//robert; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa grid,s 1-11 ground work test ok on west side of building
|
Application received | | | 6/28/2005 | | |
|
|
|
|
Issue permit | | | 6/28/2005 | | DONE |
|
|
|
|
Third Notice PLM | 8/16/2007 | 8/16/2007 | | | |
|
|
|
Second Notice has not been responded to.
|