Third Notice PLM | 3/1/2006 | 3/1/2006 | 3/2/2006 | | DONE |
|
|
|
This permit finaled on the web by Bonnie Gilbert
|
Second Notice PLM | 2/15/2006 | 2/15/2006 | 3/1/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 1/27/2006 | 1/27/2006 | 2/15/2006 | | DONE |
Bill VanDegrift
|
|
|
|
Final | 1/27/2006 | 1/27/2006 | 1/27/2006 | P | PASS |
Bill VanDegrift
|
|
|
Occ. Permit posted on the glass on the front door; Phone #: ###-#### Internet Inspection Request from: Bonnie Gilbert
|
Final | 1/26/2006 | 1/27/2006 | 1/27/2006 | A | PART |
Bill VanDegrift
|
|
|
Phone #: ###-#### Internet Inspection Request from: Bonnie Gilbert temp occ ok test dcva, pipe t&p drain to mop sink.
|
Plumbing Rough-in | 12/19/2005 | 12/20/2005 | 12/20/2005 | A | PASS |
Jim Johnson
|
|
|
Scheduled by a contractor via Hello! on 12/19/2005 at 2:38:18 PM. Contact: ###-####.
|
Plumbing Rough-in | 12/13/2005 | 12/13/2005 | 12/13/2005 | P | PART |
Jim Johnson
|
|
|
Scheduled by a contractor via Hello! on 12/13/2005 at 9:25:26 AM. Contact: ###-####. DWV system test ok
|
Plumbing Rough-in | 12/12/2005 | 12/12/2005 | 12/12/2005 | P | FAIL |
Jim Johnson
|
|
|
Scheduled by a contractor via Hello! on 12/12/2005 at 9:17:05 AM. Contact: ###-####. need to repipe vent,s to meet cross-sectional area of building drain contractor to recall when ready
|
Other | 10/21/2005 | 10/24/2005 | 10/24/2005 | A | PASS |
Jim Johnson
|
|
|
TIE-IN TO MAIN WITH DOUBLE CHECK; Phone #: ###-#### Internet Inspection Request from: Bonnie Gilbert tie -in for sprinkler and double check test ok ok to cover
|
Application received | | | 10/21/2005 | | DONE |
|
|
|
This permit was created on the web by Bonnie Gilbert
|