Second Notice PLM | 10/4/2007 | 10/4/2007 | 10/5/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 8/29/2007 | 8/29/2007 | 10/4/2007 | | DONE |
Eric Strole
|
|
|
|
Final | 8/28/2007 | 8/29/2007 | 8/29/2007 | A | PASS |
Eric Strole
|
|
|
|
Water and/or Sewer | 8/28/2007 | 8/29/2007 | 8/28/2007 | A | CANC |
Eric Strole
|
|
|
Please inspect for final in B-wing. Phone #: ###-#### Internet Inspection Request from: Carl Homola
|
Final | 8/22/2007 | 8/23/2007 | 8/23/2007 | A | PART |
Eric Strole
|
|
|
need to have shut off valve upstream of main dbcv, caulk all fixtures, need grate on flr drain in mech room, hook up trap primer in fire room, label backflow devices in kitchen, coffee makers in entry ? need permit for lawn sprinklers before final.
|
Final | 8/22/2007 | 8/22/2007 | 8/22/2007 | P | CANC |
Eric Strole
|
|
|
|
Water and/or Sewer | 8/22/2007 | 8/23/2007 | 8/22/2007 | A | CANC |
Eric Strole
|
|
|
Please inspect final for B-wing. Thanks. Phone #: ###-#### Internet Inspection Request from: Carl Homola
|
Final | 7/31/2007 | 8/1/2007 | 8/1/2007 | A | PART |
Eric Strole
|
|
|
Please inspect final - A-wing only, not B-wing. Phone #: ###-#### Internet Inspection Request from: Carl Homola-a wing final pass.
|
Other | 7/23/2007 | 7/24/2007 | 7/24/2007 | A | DONE |
Eric Strole
|
|
|
Please see Jason (foreman) for consulation re: main kitchen in B-wing. Thank you. Phone #: ###-#### Internet Inspection Request from: Carl Homola-this was a conferance on backflow devices required in kitchen area.
|
PLM-Aging Inspection | 6/25/2007 | 6/25/2007 | 6/25/2007 | | PASS |
Eric Strole
|
|
|
|
Other | 4/24/2007 | 4/24/2007 | 4/24/2007 | P | DONE |
Eric Strole
|
|
|
this was a conferance on what size flr drain for a 4" rpba. needs to be enginered.
|
Plumbing Rough-in | 4/23/2007 | 4/23/2007 | 4/23/2007 | P | PASS |
Eric Strole
|
|
|
Please inspect rough-in on all floors of B-wing. Thanks. Phone #: ###-#### Internet Inspection Request from: Carl Homola-r/i & roof drains pass.
|
Plumbing Rough-in | 4/17/2007 | 4/18/2007 | 4/18/2007 | P | PART |
Eric Strole
|
|
|
Please inspect kitchen in B-wing. Thankyou. Phone #: ###-#### Internet Inspection Request from: Carl Homola-rough-in for kitchen & beauty salon pass.
|
Plumbing Rough-in | 3/9/2007 | 3/12/2007 | 3/13/2007 | P | PART |
Eric Strole
|
|
|
Please inspect rough-in on all 3 floors of A-wing. Thanks! Phone #: ###-####-a-wing pass, still need to inspect b-wing.
|
Plumbing Rough-in | 3/12/2007 | 3/12/2007 | 3/12/2007 | P | PART |
Bill VanDegrift
|
|
|
a wing ri ok
|
Plumbing Rough-in | 2/28/2007 | 3/1/2007 | 3/1/2007 | P | PASS |
Eric Strole
|
|
|
Please inspect grease interceptor near B-wing. Thanks. Phone #: ###-####
|
PLM-Aging Inspection | 2/21/2007 | 2/21/2007 | 2/22/2007 | | PASS |
Eric Strole
|
|
|
|
Groundwork | 12/12/2006 | 12/13/2006 | 12/13/2006 | A | PART |
Eric Strole
|
|
|
Please inspect partial underground in B-wing. Thanks!; Phone #: ###-#### Internet Inspection Request from: Carl Homola-ok to cover out side fire room, jason will call when fire room g/w is complete.
|
Plumbing Rough-in | 10/10/2006 | 10/11/2006 | 10/11/2006 | P | PASS |
Eric Strole
|
|
|
Please inspect B-wing underground (full, not partial) around 12:30 if possible. Thanks!; Phone #: ###-#### Internet Inspection Request from: Carl Homola-ground work complete.
|
Groundwork | 10/5/2006 | 10/5/2006 | 10/5/2006 | P | PART |
Eric Strole
|
|
|
A wing ground work complete,still need to finish B wing.
|
Plumbing Rough-in | 10/3/2006 | 10/3/2006 | 10/3/2006 | P | CANC |
Eric Strole
|
|
|
Please inspect partial underslab of D-wing this afternoon. Thanks; Phone #: ###-#### Internet Inspection Request from: Carl Homola
|
Groundwork | 10/3/2006 | 10/3/2006 | 10/3/2006 | A | PART |
Eric Strole
|
|
|
east end of d building ground work ok.
|
Plumbing Rough-in | 10/2/2006 | 10/3/2006 | 10/3/2006 | A | CANC |
Eric Strole
|
|
|
Please inspect partial underslab of D-wing in AM; Phone #: ###-#### Internet Inspection Request from: Carl Homola
|
Groundwork | 9/27/2006 | 9/27/2006 | 9/27/2006 | P | FAIL |
Eric Strole
|
|
|
need proof that oatay # 30925 abs to pvc glue is approved for under slab connections.
|
Plumbing Rough-in | 9/27/2006 | 9/27/2006 | 9/27/2006 | P | CANC |
Eric Strole
|
|
|
Please inspect partial underslab of D-wing this afternoon. Thanks!; Phone #: ###-#### Internet Inspection Request from: Carl Homola
|
Application received | | | 9/11/2006 | | |
|
|
|
|
Issue permit | | | 9/11/2006 | | DONE |
|
|
|
|
(F) Reprint permit | | | 9/11/2006 | | DONE |
|
|
|
|