Case Summary (PLM) | | | 2/22/2008 | | DONE |
|
|
|
|
Second Notice PLM | 7/23/2007 | 7/23/2007 | 7/31/2007 | | DONE |
|
|
|
This permit finaled on the web by JENN STALEY
|
First Notice | 7/12/2007 | 7/12/2007 | 7/23/2007 | | DONE |
Eric Strole
|
|
|
|
Final | 7/11/2007 | 7/12/2007 | 7/12/2007 | A | PASS |
Eric Strole
|
|
|
JOB CONTACT RANDY REEVES Phone #: ###-#### Internet Inspection Request from: ADAM WARR-no sign off card posted.
|
Final | 6/27/2007 | 6/28/2007 | 6/28/2007 | A | PART |
Eric Strole
|
|
|
CONTACT: MIKE W Phone #: ###-#### Internet Inspection Request from: JENN STALEY-need permit for 2 rpba's,need to label non potable water & run drains to approved location.
|
Final | 5/11/2007 | 5/11/2007 | 5/11/2007 | P | PART |
Eric Strole
|
|
|
JOB CONTACT RANDY REEVES Phone #: ###-#### Internet Inspection Request from: ADAM WARR-no final on plumbing till rpba's are installed for chemical lab sink & labeled non potible water & eye wash is seperated on to potible water.
|
Plumbing Rough-in | 4/10/2007 | 4/10/2007 | 4/10/2007 | P | PART |
Eric Strole
|
|
|
JOB CONTACT: RANDY REEVES PHONE; ###-#### Phone #: ###-####-laundry room pass.
|
Other | 3/23/2007 | 3/23/2007 | 3/23/2007 | A | DONE |
Eric Strole
|
|
|
this was a conferance eith lee rice.
|
Plumbing Rough-in | 3/21/2007 | 3/22/2007 | 3/22/2007 | A | PART |
Eric Strole
|
|
|
Please contact Randy ###-#### thank you,john-ok to cover walls,there is more work to be done on existing building.
|
Owner Supplied Equipment | | | 3/21/2007 | | |
|
|
|
|
Application received | | | 3/21/2007 | | DONE |
|
|
|
This permit was created on the web by John Buss
|