Sprinkler (Final) | 10/3/2007 | 10/3/2007 | 10/3/2007 | A | PASS |
Bill VanDegrift
|
|
|
|
Sprinkler (Final) | 8/13/2007 | 8/14/2007 | 8/14/2007 | A | PART |
Jim Johnson
|
|
|
saul corvera; Phone #: ###-#### Internet Inspection Request from: Darla Downs tie in ok ok to cover still need to have double check tested and certified called contractor will recall when ready
|
Sprinkler (Final) | 8/9/2007 | 8/10/2007 | 8/10/2007 | A | FAIL |
Jim Johnson
|
|
|
###-#### saul RP cannot be installed in vault needto be 12 inches above finished grade as per table 6-2 upc need to uncover tie-in to water line and all connections for inspection upc 103.5.1.4 need to have backflow device tested and certified by a certified tester left correction notice on site and called contractor
|
Issue PAID IN FULL permit | | | 8/9/2007 | | DONE |
|
|
|
|
Application received | | | 8/9/2007 | | |
|
|
|
|