Final | 6/18/2008 | 6/18/2008 | 6/18/2008 | P | PASS |
Jim Johnson
|
|
|
|
PLM-Aging Inspection | 6/9/2008 | 6/9/2008 | 6/9/2008 | | PASS |
Jim Johnson
|
|
|
|
Final | 4/7/2008 | 4/8/2008 | 4/8/2008 | P | PART |
Jim Johnson
|
|
|
1:00 pm made walk through with Bill T. with united water and Keith Shauger from public work,s on cross control connection,s need premius protection installed need R. P. installed on truck fill station if keeping system in use or cap off in not needed need hot and cold R. P. installed on sink in garage bay area and approved signage on non-potable water need to install hose bib vaccume breaker,s on all hose bib outlet,s need to provide approved air gap or R.P. on swamp cooler water line
|
Final | 4/4/2008 | 4/7/2008 | 4/7/2008 | A | CANC |
Jim Johnson
|
|
|
|
Final | 4/3/2008 | 4/4/2008 | 4/4/2008 | A | PART |
Jim Johnson
|
|
|
Gary; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt need to make walk through with Bill T. from united water scheduled for monday 4/7/08 oked temp.
|
Application received | | | 4/3/2008 | | |
|
|
|
|
Issue permit | | | 4/3/2008 | | DONE |
|
|
|
|
First Notice | 6/18/2008 | 6/18/2008 | | | |
Jim Johnson
|
|
|
|