Final | 10/28/2008 | 10/28/2008 | 10/28/2008 | P | PASS |
Jim Johnson
|
|
|
tom Phone #: ###-####
|
Final | 10/27/2008 | 10/27/2008 | 10/27/2008 | P | PART |
Jim Johnson
|
|
|
tom Phone #: ###-#### upc 604.11.2 water heater connection with pex shall not be within 18 inches need main shut off valve on water service need gate and check valve on discharge side of ejector need to pipe T&P up staires to an approved location need R P down staires tested and certified
|
Plumbing Rough-in | 7/11/2008 | 7/14/2008 | 7/14/2008 | A | PASS |
Jim Johnson
|
|
|
jim Phone #: ###-####
|
Plumbing Rough-in | 7/11/2008 | 7/11/2008 | 7/11/2008 | P | PASS |
Jim Johnson
|
|
|
|
Plumbing Rough-in | 7/10/2008 | 7/10/2008 | 7/10/2008 | P | FAIL |
Jim Johnson
|
|
|
Tom Phone #: ###-#### need to provide shutoff valves for each dwelling unit as per upc 605.3 need to repipe each unit for softner rough-in,s need to up date permit on fixture count talked to plumber on site will recall when ready
|
Groundwork | 5/20/2008 | 5/21/2008 | 5/21/2008 | A | PASS |
Jim Johnson
|
|
|
tom Phone #: ###-####
|
Application received | | | 5/20/2008 | | |
|
|
|
|
Issue permit | | | 5/20/2008 | | DONE |
|
|
|
|