First Notice | 8/22/2008 | 8/22/2008 | 8/27/2008 | | DONE |
Eric Strole
|
|
|
|
Final | 8/19/2008 | 8/22/2008 | 8/22/2008 | A | PASS |
Eric Strole
|
|
|
BRIAN Phone #: ###-####
|
Final | 8/18/2008 | 8/18/2008 | 8/18/2008 | P | PART |
Eric Strole
|
|
|
all corrections, except suite d are complete.
|
Final | 8/18/2008 | 8/19/2008 | 8/18/2008 | A | CANC |
Eric Strole
|
|
|
Brian Phone #: ###-####
|
Other | 7/14/2008 | 7/15/2008 | 7/16/2008 | P | DONE |
Eric Strole
|
|
|
Brian- confrence Phone #: ###-####-this was a 5:00 pm conferane with dentist's about upgrades for backflow devices that need to be installed.
|
Other | 6/23/2008 | 6/24/2008 | 6/24/2008 | A | PART |
Eric Strole
|
|
|
9:00 am-need to install rpba for premis protection, need to install rpba on water supply to vacuum pumps, (suite b) need to install rpba on hot & cold supply to dishwasher & hook drain up to dishwasher tail piece, supply floor sink for rpba's, need thermal expansion tank, (suite d) need to isolate all dental chairs with rpba's.
|
Other | 6/18/2008 | 6/23/2008 | 6/23/2008 | A | PART |
Eric Strole
|
|
|
conferance-walked thru half of dental spaces, other half will be open in mourning & will leave correction notice at that time.
|
Final | 6/16/2008 | 6/16/2008 | 6/16/2008 | P | PART |
Eric Strole
|
|
|
Brian Phone #: ###-####-need to verify premis protection, temp final ok
|
Plumbing Rough-in | 6/5/2008 | 6/6/2008 | 6/6/2008 | A | PASS |
Daryl Spivey
|
|
|
brian Phone #: ###-####
|
Application received | | | 6/5/2008 | | |
|
|
|
|
Issue permit | | | 6/5/2008 | | DONE |
|
|
|
|