Sprinkler (Final) | 4/27/2009 | 4/28/2009 | 4/28/2009 | A | PASS |
Eric Strole
|
|
|
|
Sprinkler (Final) | 4/20/2009 | 4/20/2009 | 4/20/2009 | P | PART |
Eric Strole
|
|
|
rpba needs tested & certified
|
Sprinkler (Final) | 4/2/2009 | 4/2/2009 | 4/2/2009 | P | PART |
Eric Strole
|
|
|
sprinkler heads are placed below flood level of storm drainage system, this changes the degree of hazard for the backflow device installed on system. dbca needs to be replaced with a rpba.
|
CHANGE STATUS TO (I) | | | 4/2/2009 | | |
Alexandra L. DeYoung
|
|
|
per eric reopen
|
Sprinkler (Final) | 3/26/2009 | 3/27/2009 | 3/27/2009 | A | PASS |
Eric Strole
|
|
|
thad Phone #: ###-####
|
Sprinkler (Final) | 3/23/2009 | 3/24/2009 | 3/24/2009 | A | PART |
Eric Strole
|
|
|
Thad Phone #: ###-####-cannot install used dbca, ok to cover hole.
|
Application received | | | 3/23/2009 | | |
|
|
|
|
Issue permit | | | 3/23/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
First Notice | 4/28/2009 | 4/28/2009 | | | |
Eric Strole
|
|
|
|
First Notice | 3/27/2009 | 3/27/2009 | | | |
Eric Strole
|
|
|
|