First Notice | 3/24/2010 | 3/24/2010 | 11/2/2010 | | DONE |
Bill VanDegrift
|
|
|
This permit finaled on the web by Chris Field
|
PLM-Aging Inspection | 3/22/2010 | 3/22/2010 | 3/24/2010 | | PASS |
Bill VanDegrift
|
|
|
|
Final | 3/24/2010 | 3/24/2010 | 3/24/2010 | P | PASS |
Bill VanDegrift
|
|
|
corrections moved to a MIS permit
|
PLM-Aging Inspection | 1/20/2010 | 1/20/2010 | 1/20/2010 | | PART |
Bill VanDegrift
|
|
|
no calls for inspection
|
PLM-Aging Inspection | 11/19/2009 | 11/19/2009 | 11/19/2009 | | PASS |
Bill VanDegrift
|
|
|
|
PLM-Aging Inspection | 9/14/2009 | 9/14/2009 | 9/14/2009 | | PART |
Eric Strole
|
|
|
left correction notice with lee rice to mail to plumber & perkins.
|
Other | 7/13/2009 | 7/14/2009 | 7/14/2009 | A | PART |
Eric Strole
|
|
|
Water heater replacement at Perkins Restaurant. Phone #: ###-#### Internet Inspection Request from: Chris Field-Met with Bill Thompson with United Water for a walk thru for backflow pervention.1-need one rpba to serve the coffee machine, ice tea maker and hot water dispensor. 2-need a rpba on ice machine upstream of filter system. 3-need a rpba on dishwasher. 4-need a dbca on juicer. 5-need a dbca on hot cocoa machine. 6-need seperate water supply for soap dispensor at mop sink. 7-softner drain requires an air gap. 8-all backflow devices need tested & certified. Left correction notice on site.
|
Other | 7/13/2009 | 7/13/2009 | 7/13/2009 | P | NR |
Bill VanDegrift
|
|
|
This is at the Perkins Restaurant. (Couldn''t tell by the address selection on the PDS if I had the right lot/block) Water heater replacement. Water heater has outside access. Phone #: ###-#### Internet Inspection Request from: Chris Field- will have walk-thru with bill thompson for backflow protection 7-14-09.
|
Application received | | | 7/13/2009 | | DONE |
|
|
|
This permit was created on the web by Chris Field
|