PLM-Aging Inspection | 4/12/2010 | 4/12/2010 | 4/12/2010 | | PASS |
Jim Johnson
|
|
|
|
DOC - Permit Expired | 4/12/2010 | 4/12/2010 | 4/12/2010 | P | PASS |
Jim Johnson
|
|
|
|
Water and/or Sewer | 7/22/2009 | 7/22/2009 | 7/22/2009 | A | FAIL |
Eric Strole
|
|
|
need to support pex in crawl every 32". #1 ballvalve on rpba is where the #2 ballvalve should be. need thermal expantion tank down stream of dbca. rpba & dbca need tested & certified. ok to cover waterline.
|
Water and/or Sewer | 7/20/2009 | 7/20/2009 | 7/20/2009 | P | FAIL |
Eric Strole
|
|
|
rpba for landscape needs to be a minimum of 12" above grade to dump cup, need to sleve waterline 10' each side of where it crosses sewer, only 1 hose clamp connection under house(need to use approved material downstream of shutoff valve under house) & 3 plexes and above require premis protection (need dbca on water supply) all backflows need tested & certified.
|
Application received | | | 7/20/2009 | | |
|
|
|
|
Issue permit | | | 7/20/2009 | | DONE |
|
|
|
|