Final | 2/2/2010 | 2/2/2010 | 2/2/2010 | P | PASS |
Bill VanDegrift
|
|
|
John Phone #: ###-####
|
Plumbing Rough-in | 9/29/2009 | 9/29/2009 | 9/29/2009 | P | PASS |
Bill VanDegrift
|
|
|
john Phone #: ###-#### ri ok
|
Plumbing Rough-in | 9/28/2009 | 9/28/2009 | 9/28/2009 | P | FAIL |
Bill VanDegrift
|
|
|
John Phone #: ###-#### laundry tray venting must be above the trap. laundry waste must enter horizontal waste using a wye fitting. kitchen sink waste must be 2" vent 1 1/2". all horizontal to horizontal waste must be made with a wye fitting. test waste and vent and water systems. glue concealled nuts in traps or use solvent weld traps.
|
Application received | | | 9/28/2009 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/28/2009 | | DONE |
|
|
|
|