First Notice | 8/26/2010 | 8/26/2010 | 1/3/2011 | | DONE |
Jim Johnson
|
|
|
This permit finaled on the web by PATTY KIRK
|
Final | 8/25/2010 | 8/26/2010 | 8/26/2010 | A | PASS |
Jim Johnson
|
|
|
|
Final | 8/23/2010 | 8/25/2010 | 8/25/2010 | A | PART |
Jim Johnson
|
|
|
Phone #: ###-#### >> Inspection requested via web by PATTY KIRK need to repipe T&P drain line so it is not trapped reschedule final inspection for 8/26/10 am
|
Final | 8/20/2010 | 8/23/2010 | 8/23/2010 | P | PART |
Jim Johnson
|
|
|
Phone #: ###-#### >> Inspection requested via web by PATTY KIRK as per 2003 upc 508.5 discharge from a relief valve in to a water heater pan shall be prohibited. need to pipe relief valve drain line to mop sink . need to have final sign off card on site. called contractor need to recall when ready
|
Final | 8/19/2010 | 8/20/2010 | 8/20/2010 | P | CANC |
Jim Johnson
|
|
|
Phone #: ###-#### >> Inspection requested via web by PATTY KIRK canc by contractor
|
Plumbing Rough-in | 7/16/2010 | 7/19/2010 | 7/19/2010 | A | PASS |
Jim Johnson
|
|
|
|
Plumbing Rough-in | 7/16/2010 | 7/16/2010 | 7/16/2010 | P | CANC |
Jim Johnson
|
|
|
Aaron ###-#### Phone #: ###-#### >> Inspection requested via web by PATTY KIRK reschedule rough-in inspection with Aaron for 7/19/10 am
|
Groundwork | 7/6/2010 | 7/7/2010 | 7/7/2010 | A | PASS |
Jim Johnson
|
|
|
Inspection requested from web by: PATTY KIRK Phone #: ###-####
|
Application received | | | 7/6/2010 | | DONE |
|
|
|
This permit was created on the web by PATTY KIRK
|