First Notice | | 10/7/2011 | 10/14/2011 | | DONE |
|
|
|
This permit finaled on the web by Kirk Johns
|
Final | 8/16/2011 | 8/16/2011 | 8/16/2011 | A | PASS |
Jim Johnson
|
|
|
Final inspection on plumbing at Kohls Phone #: ###-#### >> Inspection requested via web by Kirk Johns
|
Plumbing Rough-in | 7/26/2011 | 7/27/2011 | 7/27/2011 | A | PASS |
Jim Johnson
|
|
|
Rough-in for first floor mop sink area Phone #: ###-#### >> Inspection requested via web by Kirk Johns
|
Plumbing Rough-in | 6/16/2011 | 6/16/2011 | 6/16/2011 | P | PART |
Jim Johnson
|
|
|
Walk through of project on second floor Phone #: ###-#### >> Inspection requested via web by Kirk Johns walk through with plumbing contractor
|
Plumbing Rough-in | 5/26/2011 | 5/27/2011 | 5/27/2011 | A | PASS |
Jim Johnson
|
|
|
restroom,s test ok ok to cover
|
Plumbing Rough-in | 5/25/2011 | 5/26/2011 | 5/26/2011 | P | FAIL |
Jim Johnson
|
|
|
Early pm would be preferrable if possible. Contact Aaron with any questions. Thanks Phone #: ###-#### >> Inspection requested via web by Kirk Johns need to correct leak,s in D W V need to replace 4x2 san tee with 4x2 combo,s for urinal connection need to replace galv. 90 with approved durham drainage 90 on urinal,s and drinking fountain need mid story support,s on main 4 inch stack .need base of stack cleanout installed on main 4 inch waste stack.
|
Groundwork | 5/17/2011 | 5/18/2011 | 5/18/2011 | A | PASS |
Jim Johnson
|
|
|
I requested this inspection yesterday but have not seen an inspector yet today. I do not know if there was a computer error so please ignore if this is a duplication. Call Bob ###-#### with any questions. Phone #: ###-#### >> Inspection requested via web by Kirk Johns
|
Application received | | | 4/13/2011 | | DONE |
|
|
|
This permit was created on the web by Kirk Johns
|