Final | 10/12/2011 | 10/13/2011 | 10/13/2011 | A | PASS |
Jim Johnson
|
|
|
JOB # 16006. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes
|
Final | 10/13/2011 | 10/13/2011 | 10/13/2011 | P | CANC |
Jim Johnson
|
|
|
JOB # 16006. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes Inspection cancelled from web by: Ann Marie Reyes
|
Plumbing Rough-in | 8/19/2011 | 8/19/2011 | 8/19/2011 | P | PASS |
Jim Johnson
|
|
|
JOB # 16006. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes
|
Plumbing Rough-in | 8/18/2011 | 8/19/2011 | 8/19/2011 | A | FAIL |
Jim Johnson
|
|
|
JOB # 16006. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes as per 906.2 vent shall terminate 10 feet or 3 feet above openable window need to move 2 inch vent from master bath from upstaires window note - D W V and water test ok contractor to recall when ready correction notice on site
|
Application received | | | 8/15/2011 | | DONE |
|
|
|
This permit was created on the web by Ann Marie Reyes
|