First Notice | 7/1/2014 | 7/1/2014 | 12/17/2014 | | DONE |
Jim Johnson
|
|
|
This permit finaled on the web by Stacia Haumann
|
Print Statement | | | 12/16/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Final | 7/1/2014 | 7/1/2014 | 7/1/2014 | P | PASS |
Jim Johnson
|
|
|
if questions call Matt @ ###-####. Phone #: ###-#### >> Inspection requested via web by Stacia Haumann
|
Plumbing Rough-in | 5/22/2014 | 5/22/2014 | 5/22/2014 | P | PART |
Jim Johnson
|
|
|
if questions call Matt @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann repipe of water and med air and vac 2nd floor south tower water test ok start of 24 pressure test on med gas portion
|
Final | 5/14/2014 | 5/14/2014 | 5/14/2014 | P | PART |
Jim Johnson
|
|
|
PARTIAL Final. if questions call Matt ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann final for trauma / ed area ok
|
Plumbing Rough-in | 4/4/2014 | 4/7/2014 | 4/7/2014 | A | PART |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann 24 hr pressure test in x-ray test ok on med gas
|
Plumbing Rough-in | 4/2/2014 | 4/2/2014 | 4/2/2014 | P | PASS |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann rough-in marked on plan for E R area test ok ok to cover
|
Med/Gas Systems | 4/1/2014 | 4/2/2014 | 4/2/2014 | A | PASS |
Jim Johnson
|
|
|
24 hr pressure test in E R area test ok marked on plan
|
Med/Gas Systems | 3/31/2014 | 4/1/2014 | 4/1/2014 | A | PART |
Jim Johnson
|
|
|
Rough In. If questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann start of 24 hr pressure test marked on plan
|
Plumbing Rough-in | 3/24/2014 | 3/25/2014 | 3/25/2014 | A | PART |
Jim Johnson
|
|
|
if questions call Dustin @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann overhead water hot and cold and hard water in trauma area test ok
|
Med/Gas Systems | 3/19/2014 | 3/20/2014 | 3/20/2014 | P | PART |
Jim Johnson
|
|
|
24 hr pressure test in trauma area test ok
|
Plumbing Rough-in | 3/18/2014 | 3/19/2014 | 3/19/2014 | P | PART |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann in wall water rough-in and D W V rough-in with vent,s through roof test ok ok to cover start of 24 hr pressure test on med gas in trauma area
|
Groundwork | 2/25/2014 | 2/26/2014 | 2/26/2014 | A | PASS |
Bill VanDegrift
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann gw ok
|
Groundwork | 2/17/2014 | 2/18/2014 | 2/18/2014 | A | PART |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann ground work for phase 3 part 1 test ok ok to cover
|
Final | 12/17/2013 | 12/18/2013 | 12/18/2013 | A | PART |
Jim Johnson
|
|
|
Questions please call Mark ###-#### >> Inspection requested via web by Stacia Haumann final on area,s marked on plumbing contractor plan
|
Plumbing Rough-in | 11/13/2013 | 11/13/2013 | 11/13/2013 | A | PASS |
Jim Johnson
|
|
|
D W V and water rough-in for phase two test ok ok to cover
|
Med/Gas Systems | 11/12/2013 | 11/13/2013 | 11/13/2013 | A | PART |
Jim Johnson
|
|
|
24hr pressure test for med gas test ok in phase two
|
Plumbing Rough-in | 11/8/2013 | 11/12/2013 | 11/12/2013 | A | PART |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann start of 24 hr med gas pressure test
|
Groundwork | 11/8/2013 | 11/12/2013 | 11/8/2013 | A | CANC |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann Inspection cancelled from web by: Stacia Haumann
|
Plumbing Rough-in | 10/29/2013 | 10/30/2013 | 10/30/2013 | A | PASS |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann rough-in for two restroom,s and breakroom sink test ok ok to cover
|
Groundwork | 10/17/2013 | 10/17/2013 | 10/17/2013 | P | PASS |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann groundwork on south east side of building test ok ok to cover
|
Groundwork | 10/16/2013 | 10/16/2013 | 10/16/2013 | P | PASS |
Jim Johnson
|
|
|
groundwork in north-east corner of building test ok
|
Groundwork | 10/15/2013 | 10/16/2013 | 10/16/2013 | A | NR |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann not ready
|
Final | 9/10/2013 | 9/10/2013 | 9/11/2013 | P | PART |
Jim Johnson
|
|
|
Final for PHASE 2A ONLY. Please call Mark Prior to Arrival ###-####. Phone #: ###-#### >> Inspection requested via web by Stacia Haumann final on phase 2A ok
|
Med/Gas Systems | 7/1/2013 | 7/2/2013 | 7/2/2013 | A | PART |
Jim Johnson
|
|
|
24 hr pressure test on oxygen line test ok
|
Plumbing Rough-in | 6/28/2013 | 7/1/2013 | 7/1/2013 | A | PART |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann med gas 24 hr pressure test on vac and nitrous test ok start of 24 hr pressure test for oxygen
|
Plumbing Rough-in | 6/28/2013 | 6/28/2013 | 6/28/2013 | P | PART |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann start of 24 hr pressure test on med gas
|
Plumbing Rough-in | 6/26/2013 | 6/27/2013 | 6/27/2013 | P | PASS |
Jim Johnson
|
|
|
if questions call Mark @ ###-####. Phone #: ###-#### >> Inspection requested via web by Stacia Haumann
|
Plumbing Rough-in | 6/26/2013 | 6/26/2013 | 6/26/2013 | P | PART |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann D W V on south side of new addition test ok all over head and in wall water test ok
|
Plumbing Rough-in | 6/11/2013 | 6/12/2013 | 6/12/2013 | A | PART |
Jim Johnson
|
|
|
IF QUESTIONS CALL MARK @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann hard water trunk line test ok
|
Plumbing Rough-in | 6/7/2013 | 6/10/2013 | 6/10/2013 | A | PART |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann over head cw , hw and hw return line trunk line only marked on plan test ok
|
Groundwork | 6/7/2013 | 6/10/2013 | 6/10/2013 | A | PART |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann moved sink in groundwork test ok ok to cover marked on plan
|
Groundwork | 5/20/2013 | 5/21/2013 | 5/21/2013 | A | PASS |
Jim Johnson
|
|
|
IF QUESTIONS CALL MARK @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann phase two groundwork complete
|
Groundwork | 5/6/2013 | 5/6/2013 | 5/6/2013 | P | PART |
Jim Johnson
|
|
|
if questions please contact Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann men and women rest room in south-east corner test ok ok to cover
|
Groundwork | 4/26/2013 | 4/29/2013 | 4/29/2013 | A | PART |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann groundwork for phase 2 east side of building test ok ok to cover noted on plans
|
Groundwork | 3/26/2013 | 3/26/2013 | 3/26/2013 | P | PASS |
Jim Johnson
|
|
|
if questions call Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann
|
Final | 3/4/2013 | 3/5/2013 | 3/5/2013 | A | PART |
Jim Johnson
|
|
|
**FINAL is ONLY for Phase 1. Per Mark Mansfield & Jim Johnson conversation, permit is now linked to correct Bld permit. Please final out in computer. if questions call Stacia @ ###-#### or Mark @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann final on phase 1 ok
|
Final | 3/1/2013 | 3/1/2013 | 3/1/2013 | A | PART |
Jim Johnson
|
|
|
final on phase 1 ok
|
Final | 2/25/2013 | 2/26/2013 | 2/26/2013 | A | PART |
Jim Johnson
|
|
|
this is a Final for PHASE 1 ONLY, there will be other phases being called in on this permit at a later date. so please dont close it out. please call Mark 30 mins prior to arrival, he will need to walk you through the job site ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann need med gas certification for phase 1
|
Other | 2/25/2013 | 2/26/2013 | 2/25/2013 | A | CANC |
Jim Johnson
|
|
|
this is a Final for PHASE 1 ONLY, there will be other phases being called in on this permit at a later date. so please dont close it out. Phone #: ###-#### >> Inspection requested via web by Stacia Haumann Inspection cancelled from web by: Stacia Haumann
|
Med/Gas Systems | 2/4/2013 | 2/5/2013 | 2/5/2013 | A | PASS |
Jim Johnson
|
|
|
24 hr pressure test ok
|
Plumbing Rough-in | 2/1/2013 | 2/4/2013 | 2/4/2013 | A | PART |
Jim Johnson
|
|
|
med gas RI, please call Mark 30 mins prior, he will need to meet you and walk you through the project ###-####. Phone #: ###-#### >> Inspection requested via web by Stacia Haumann start of 24 hr pressure test on piping in E R
|
Plumbing Rough-in | 1/25/2013 | 1/28/2013 | 1/28/2013 | A | PART |
Jim Johnson
|
|
|
MED GAS RI Please call Mark 30 mins prior so he can walk you through the job site. ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann portion of med gas 24hr test marked on plan test ok
|
Plumbing Rough-in | 1/24/2013 | 1/25/2013 | 1/25/2013 | A | PART |
Jim Johnson
|
|
|
please call Mark 30 mins prior so he can walk you through the project. ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann start of 24 hr pressure test on med gas on station on north side
|
Plumbing Rough-in | 1/23/2013 | 1/24/2013 | 1/24/2013 | P | PART |
Jim Johnson
|
|
|
please call Mark 30 mins prior, he will need to walk you through the project. ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann rough in on sink,s marked on plan test ok ok to cover
|
Plumbing Rough-in | 1/17/2013 | 1/18/2013 | 1/18/2013 | A | PASS |
Jim Johnson
|
|
|
|
Plumbing Rough-in | 1/16/2013 | 1/17/2013 | 1/17/2013 | A | PART |
Jim Johnson
|
|
|
requested 9am if possible (this is in a "clean area") Please contact Mark to schedule, as he will need to walk you through the project. Phone #: ###-#### >> Inspection requested via web by Stacia Haumann conf only
|
Plumbing Rough-in | 1/8/2013 | 1/9/2013 | 1/9/2013 | A | PART |
Daryl Spivey
|
|
|
for Roof Drains. If questions please call Mark @ ###-####. **PLEASE call 30 mins prior to arrival, Mark will need to walk with you through the project** Phone #: ###-#### >> Inspection requested via web by Stacia Haumann 2 roof drains test ok as marked on plans........ds
|
Med/Gas Systems | 1/7/2013 | 1/8/2013 | 1/8/2013 | P | PASS |
Jim Johnson
|
|
|
24 hr pressure test test ok
|
Plumbing Rough-in | 1/4/2013 | 1/7/2013 | 1/7/2013 | P | PART |
Jim Johnson
|
|
|
Med Gas. Please call Mark 30 mins prior, he needs to meet you to walk you through the project. ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann start of 24 hr pressure test
|
Plumbing Rough-in | 12/28/2012 | 1/2/2013 | 1/2/2013 | P | PART |
Jim Johnson
|
|
|
Please call Mark Prior to showing up so he can meet you to walk you through job site. ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann rough-in marked on plan test ok
|
Groundwork | 12/28/2012 | 1/2/2013 | 1/2/2013 | P | PASS |
Jim Johnson
|
|
|
Please call Mark Prior to showing up so he can meet you to walk you through job site. ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann
|
Plumbing Rough-in | 12/27/2012 | 12/28/2012 | 12/28/2012 | P | PART |
Jim Johnson
|
|
|
Please call Mark 30 mins prior so he has time to come out and meet you to walk you through, ###-####. Phone #: ###-#### >> Inspection requested via web by Stacia Haumann rough-in marked on plan,s test ok ok to cover
|
Groundwork | 11/20/2012 | 11/21/2012 | 11/21/2012 | P | PART |
Jim Johnson
|
|
|
GW FOR EXTERIOR. If questions call Matt @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann groundwork marked on plan test ok ok to cover
|
Groundwork | 11/20/2012 | 11/21/2012 | 11/21/2012 | A | PART |
Jim Johnson
|
|
|
GW FOR INTERIOR. If questions call Matt @ ###-#### Phone #: ###-#### >> Inspection requested via web by Stacia Haumann groundwork marked on plan,s test ok
|
Groundwork | 11/8/2012 | 11/9/2012 | 11/9/2012 | A | PART |
Jim Johnson
|
|
|
If ?''s, call Mark Mansfield ####-####. Phone #: ###-#### >> Inspection requested via web by Stacia Haumann new trunk line marked on plan,s test ok
|
Issue PAID IN FULL permit | | | 10/17/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/17/2012 | | DONE |
|
|
|
This permit was created on the web by Stacia Haumann
|