Final | 6/11/2014 | 6/11/2014 | 6/11/2014 | P | PASS |
Eric Strole
|
|
|
JOB # 17371. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes
|
Plumbing Rough-in | 4/11/2014 | 4/11/2014 | 4/11/2014 | P | PASS |
Eric Strole
|
|
|
JOB # 17371. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes
|
Plumbing Rough-in | 4/10/2014 | 4/11/2014 | 4/11/2014 | A | FAIL |
Eric Strole
|
|
|
JOB # 17371. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes-Still need to fix backgrade on 3" in garage overhead next to the exteriour of unit.
|
Plumbing Rough-in | 4/9/2014 | 4/10/2014 | 4/10/2014 | P | FAIL |
Eric Strole
|
|
|
JOB # 17371. Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes-Need to fix reverse grade on 3" horizontal drain in garage overhead .Need to be 6" above flood level rim before going horizontal with vent. (KITCHEN SINK) Need to test all dwv.
|
Issue PAID IN FULL permit | | | 4/8/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/8/2014 | | DONE |
|
|
|
This permit was created on the web by Ann Marie Reyes
|