Final | 6/4/2014 | 6/4/2014 | 6/4/2014 | P | PASS |
Eric Strole
|
|
|
|
Final | 6/3/2014 | 6/4/2014 | 6/4/2014 | A | FAIL |
Eric Strole
|
|
|
Todd-boiler inspection final Phone #: ###-####-need to run T&P to an approved location and need to install a drip leg on gas line before regulator
|
Other | 5/6/2014 | 5/7/2014 | 5/7/2014 | A | PASS |
Eric Strole
|
|
|
60 lb gas test pass
|
Other | 5/5/2014 | 5/6/2014 | 5/6/2014 | A | FAIL |
Eric Strole
|
|
|
Todd-Hydronic test Phone #: ###-####-Need 60 lb gas test and 100lb hydronic test.
|
Issue PAID IN FULL permit | | | 5/5/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/5/2014 | | DONE |
|
|
|
This permit was created on the web by Steve Marcus
|
First Notice | 6/4/2014 | 6/4/2014 | | | |
Eric Strole
|
|
|
|