Final | 4/12/2015 | 4/13/2015 | 4/13/2015 | A | PASS |
Eric Strole
|
|
|
Please call for code access. Thanks Phone #: ###-#### Inspection requested via web by Jason Gonzalez
|
Plumbing Rough-in | 11/25/2014 | 11/25/2014 | 11/25/2014 | P | PASS |
Eric Strole
|
|
|
Please call with any questions. Phone #: ###-#### Inspection requested via web by Jason Gonzalez
|
Issue PAID IN FULL permit | | | 11/25/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/25/2014 | | DONE |
|
|
|
This permit was created on the web by Jason Gonzalez
|