Sprinkler (Final) | 5/20/2015 | 5/21/2015 | 5/21/2015 | A | PASS |
Bill VanDegrift
|
|
|
Re-Inspect for Mayfield Landscaping Phone #: ###-#### Inspection requested via web by Abram Neider final ok with union at the dcva
|
Sprinkler (Final) | 5/14/2015 | 5/15/2015 | 5/15/2015 | P | FAIL |
Bill VanDegrift
|
|
|
Phone #: ###-#### In1) spection requested via web by Abram Neider 1) need unions at dcva. 2) need two clamps at each joint (upstream joint has one clamp on barbed fitting)
|
Issue PAID IN FULL permit | | | 5/14/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/6/2015 | | DONE |
|
|
|
This permit was created on the web by Abram Neider
|