Final | 11/18/2015 | 11/18/2015 | 11/18/2015 | A | PASS |
Jim Little
|
|
|
lowered service sink as per GC Phone #: ###-#### Inspection requested via web by Raul Castanon >final ok, could not find sign off card
|
Final | 11/6/2015 | 11/6/2015 | 11/6/2015 | A | FAIL |
Jim Little
|
|
|
3/4 rp in compressor room for all 3 hose bibs Phone #: ###-#### Inspection requested via web by Raul Castanon >rp ok >service sink is s-trapped and bushed down from a 2" trap to a 1.5" trap arm and abs is glued to pvc. repipe sink correctly
|
Final | 10/30/2015 | 10/30/2015 | 10/30/2015 | P | PART |
Bill VanDegrift
|
|
|
set all equipment and call for a final inspection
|
Other | 10/29/2015 | 10/30/2015 | 10/30/2015 | A | DONE |
Jim Little
|
|
|
meet Stacy from united water on hose bibbs 9:00. >Stacey is requiring rpba on hose bibbs in shop, vertical rpba's ok if approved.
|
Final | 10/22/2015 | 10/22/2015 | 10/22/2015 | A | FAIL |
Jim Little
|
|
|
Phone #: ###-#### Inspection requested via web by Raul Castanon >All hosebibbs in the shop area must be protected by a RP backflow assembly per the water purveyor. (united water) >leak at solder joint on s. hb.
|
Final | 10/12/2015 | 10/12/2015 | 10/13/2015 | P | PASS |
Jim Little
|
|
|
Phone #: ###-#### Inspection requested via web by Raul Castanon >Need RPBA on shop hose bibbsshop >cut out vinyl roof to full size of pipe north end roof drain and overflow, install baskets.
|
CHANGE STATUS TO (I) | | | 10/13/2015 | | DONE |
|
|
|
as per Jim Little-was finaled by mistake
|
Roof Drains | 9/22/2015 | 9/22/2015 | 9/22/2015 | A | FAIL |
Jim Little
|
|
|
Phone #: ###-#### Inspection requested via web by Raul Castanon >add c/o per 1101.12.2 >support pvc every 4' per tbl 3-2 all sizes
|
Water and/or Sewer | 9/15/2015 | 9/15/2015 | 9/15/2015 | A | PART |
Jim Little
|
|
|
Talk to Bill Vandergriff regarding sample ports. they are not needed Phone #: ###-#### Inspection requested via web by Raul Castanon >incp venting ok >incp inlet and outlet ok >incp 24 test ok
|
Water and/or Sewer | 9/11/2015 | 9/11/2015 | 9/11/2015 | P | FAIL |
Jim Little
|
|
|
Sand and grease vault, drain and vent Phone #: ###-#### Inspection requested via web by Raul Castanon >not under test >tank needs to be vented seperate, not on the pipe inlet. >outlet need two way C/O and sampling port, wye combo does not work for sampling port.
|
Plumbing Rough-in | 8/26/2015 | 8/26/2015 | 8/26/2015 | P | PART |
Jim Little
|
|
|
tee''s are in for hammer aresters, will install at trim. Framer will frame a 12x12 accsses Phone #: ###-#### Inspection requested via web by Raul Castanon >bathroom area ri ok
|
Plumbing Rough-in | 8/21/2015 | 8/21/2015 | 8/21/2015 | P | FAIL |
Jim Little
|
|
|
public restrooms only Phone #: ###-#### Inspection requested via web by Raul Castanon 1>dwv test fail-leaks 2>backgraded vents 3>venting not per approved plans, change vent size at tee not bushing in a 90. 4>strap 3" drain at strut 5>add hammer arrestor for urnals.
|
Plumbing Rough-in | 8/20/2015 | 8/21/2015 | 8/21/2015 | A | FAIL |
Jim Little
|
|
|
Public restrooms only Phone #: ###-#### Inspection requested via web by Raul Castanon >leaks in DWV system
|
Groundwork | 6/1/2015 | 6/1/2015 | 6/1/2015 | P | PART |
Bill VanDegrift
|
|
|
gw ok with vent at tire changing tank floor drain. vents for interceptor are not installed yet will call when ready.
|
Groundwork | 6/1/2015 | 6/1/2015 | 6/1/2015 | P | FAIL |
Jim Little
|
|
|
Phone #: ###-#### Inspection requested via web by Raul Castanon. No approved plans available, tire changer FD needs a vent.
|
Water and/or Sewer | 5/28/2015 | 5/28/2015 | 5/28/2015 | A | PART |
Bill VanDegrift
|
|
|
Phone #: ###-#### Inspection requested via web by Raul Castanon partial gw ok restroom area
|
Issue PAID IN FULL permit | | | 5/28/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 5/28/2015 | | |
|
|
|
|
Application received | | | 5/28/2015 | | DONE |
|
|
|
This permit was created on the web by Raul Castanon
|
First Notice | 11/18/2015 | 11/18/2015 | | | |
Jim Little
|
|
|
|
First Notice | 10/13/2015 | 10/13/2015 | | | |
Jim Little
|
|
|
|