Final | 10/8/2015 | 10/9/2015 | 10/9/2015 | A | PASS |
Bill VanDegrift
|
|
|
Phone #: ###-#### Inspection requested via web by Scott Myers
|
Final | 10/5/2015 | 10/6/2015 | 10/6/2015 | A | FAIL |
Jim Little
|
|
|
Inspector Plz Call me for entry details Phone #: ###-#### Inspection requested via web by Scott Myers >install pan with drain under water heater(508.4 ispc) >use approved material on t&p, pvc is not approved, and turn down 90 outside.(608.5 ispc)
|
Plumbing Rough-in | 6/8/2015 | 6/9/2015 | 6/9/2015 | A | PASS |
Jim Little
|
|
|
Scott Phone #: ###-####
|
Plumbing Rough-in | 6/6/2015 | 6/8/2015 | 6/8/2015 | A | FAIL |
Jim Little
|
|
|
North door, right side of garage for entry Phone #: ###-#### Inspection requested via web by Scott Myers====WC vent must be 6" over flood level rim before horizontal offset per 905.3 UPC, Nail plates must extend 1.5" past OD of pipe per 313.9 UPC, please correct and reschedule.
|
Issue PAID IN FULL permit | | | 6/3/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Issue PAID IN FULL permit | | | 6/3/2015 | | DONE |
|
|
|
|
Application received | | | 6/3/2015 | | |
|
|
|
|