First Notice | 10/7/2015 | 10/7/2015 | 10/16/2015 | | DONE |
Jim Little
|
|
|
This permit finaled on the web by Chris Field
|
First Notice | 10/6/2015 | 10/6/2015 | 10/16/2015 | | DONE |
Jim Little
|
|
|
This permit finaled on the web by Chris Field
|
Final | 10/7/2015 | 10/7/2015 | 10/7/2015 | P | PASS |
Jim Little
|
|
|
final reinspect Phone #: ###-#### Inspection requested via web by Chris Field
|
Final | 10/6/2015 | 10/6/2015 | 10/6/2015 | P | FAIL |
Jim Little
|
|
|
TENANT IMPROVEMENT FINAL TRIM Phone #: ###-#### Inspection requested via web by Chris Field >caulk around mop sink >add temp limiting device that is ASSE 1070 certified on both lavs to limit hot water to 120 degrees or less. per 413.1 upc
|
Final | 10/6/2015 | 10/6/2015 | 10/6/2015 | P | FAIL |
Jim Little
|
|
|
TENANT IMPROVEMENT FINAL TRIM Phone #: ###-#### Inspection requested via web by Chris Field >caulk around mop sink >add temp limiting device that is ASSE 1070 certified on both lavs to limit hot water to 120 degrees or less. per 413.1 upc
|
CHANGE STATUS TO (I) | | | 10/6/2015 | | DONE |
|
|
|
as per Jim Little-finaled by mistake
|
Plumbing Rough-in | 9/16/2015 | 9/16/2015 | 9/16/2015 | P | PASS |
Jim Little
|
|
|
STEVE RADY, CONTRACTOR. Phone #: ###-#### Inspection requested via web by Chris Field
|
Plumbing Rough-in | 9/15/2015 | 9/15/2015 | 9/15/2015 | P | FAIL |
Jim Little
|
|
|
STEVE RADY, CONTRACTOR, ###-#### Phone #: ###-#### Inspection requested via web by Chris Field >1 Need permanent glue caps on demoed plumbing. >2 Santee not approved for horizontal use @ wb >3 must be 6" above flood level rim before turning horizontal @ mop sink upc 905.3 >4 leak at nipple on hot side of wh loop. >5 retest and re inspect
|
Groundwork | 8/24/2015 | 8/25/2015 | 8/25/2015 | A | PASS |
Jim Little
|
|
|
steve rady Phone #: ###-#### Inspection requested via web by Chris Field
|
Groundwork | 8/24/2015 | 8/24/2015 | 8/24/2015 | P | FAIL |
Jim Little
|
|
|
GROUNDWORK Phone #: ###-#### Inspection requested via web by Chris Field >DWV test fail, need 10' head >Wye at mop sink for vent installed backwards
|
Groundwork | 8/20/2015 | 8/21/2015 | 8/21/2015 | P | NR |
Jim Little
|
|
|
STEVE RADY, ###-#### Phone #: ###-#### Inspection requested via web by Chris Field
|
Issue PAID IN FULL permit | | | 8/20/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 8/20/2015 | | |
|
|
|
|
Application received | | | 8/20/2015 | | DONE |
|
|
|
This permit was created on the web by Chris Field
|