First Notice | 4/13/2016 | 4/13/2016 | 7/6/2016 | | DONE |
Eric Strole
|
|
|
This permit finaled on the web by Brent Lacy
|
Final | 4/13/2016 | 4/13/2016 | 4/13/2016 | P | PASS |
Eric Strole
|
|
|
|
Final | 4/12/2016 | 4/13/2016 | 4/13/2016 | A | PART |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Brent Lacy-Need seperate waterline for soap dispensor at mop sink.Temp final ok
|
Final | 4/8/2016 | 4/8/2016 | 4/8/2016 | P | FAIL |
Eric Strole
|
|
|
Please make this around 4:00 if possible to insure that the Backflow tester has made it there. Phone #: ###-#### Inspection requested via web by Brent Lacy-The vent for the vapor compartment on the fuel interceptor shall be independently vented.(cannot tie into ant other vent) T&P for water heater requires an air-gap.
|
Water and/or Sewer | 4/8/2016 | 4/8/2016 | 4/8/2016 | P | CANC |
Eric Strole
|
|
|
Please make this around 4:00 if possible to insure that the Backflow tester has made it there. Phone #: ###-#### >> Inspection requested via web by Brent Lacy Inspection cancelled from web by: Brent Lacy
|
Water and/or Sewer | 2/29/2016 | 2/29/2016 | 2/29/2016 | P | PART |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Brent Lacy-Water and sewer pass.
|
Water and/or Sewer | 2/26/2016 | 2/29/2016 | 2/29/2016 | A | FAIL |
Eric Strole
|
|
|
Please schedule for late morning. Around 10:30-11 am. Thank you! Phone #: ###-#### Inspection requested via web by Brent Lacy-Corrections not complete
|
Water and/or Sewer | 2/25/2016 | 2/26/2016 | 2/26/2016 | P | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Brent Lacy-Sewer not complete, need test on sewer. Need clean fill under and around water and sewer. Test on water pass.
|
Plumbing Rough-in | 2/9/2016 | 2/10/2016 | 2/10/2016 | A | PART |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Brent Lacy-Store area rough-in pass.
|
Other | 1/19/2016 | 1/19/2016 | 1/19/2016 | P | PART |
Eric Strole
|
|
|
Grease interceptor has been piped with 6" through tank. Need reinspection. Phone #: ###-#### Inspection requested via web by Brent Lacy-Test on interceptor pass. Still need sewer tie-in.
|
Other | 1/15/2016 | 1/19/2016 | 1/19/2016 | A | CANC |
Eric Strole
|
|
|
Need inspection for flammable liquids interceptor and car wash tank. Phone #: ###-#### >> Inspection requested via web by Brent Lacy Inspection cancelled from web by: Brent Lacy
|
Other | 1/15/2016 | 1/15/2016 | 1/15/2016 | P | FAIL |
Bill VanDegrift
|
|
|
need to pipe through the tank with 6" per plans
|
Groundwork | 12/23/2015 | 12/23/2015 | 12/23/2015 | P | PART |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Brent Lacy-G/W inside building pass. Still need carwash.
|
Water and/or Sewer | 12/22/2015 | 12/22/2015 | 12/22/2015 | P | PART |
Eric Strole
|
|
|
Waterline into building and 10' out side of building test ok. Need tracer wire.
|
Groundwork | 12/21/2015 | 12/22/2015 | 12/22/2015 | A | PART |
Eric Strole
|
|
|
Inspection needed first thing in the morning. Inspection requested via web by Brent Lacy-Section complete is marked on plans
|
Issue PAID IN FULL permit | | | 12/21/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/21/2015 | | DONE |
|
|
|
This permit was created on the web by Brent Lacy
|