Final | 5/4/2016 | 5/5/2016 | 5/5/2016 | A | PASS |
Eric Strole
|
|
|
8:00 AM
|
Final | 5/4/2016 | 5/4/2016 | 5/4/2016 | A | PASS |
Eric Strole
|
|
|
call for garage code Phone #: ###-#### Inspection requested via web by Todd Walter
|
DOC - Permit Finaled | 5/4/2016 | 5/4/2016 | 5/4/2016 | P | PASS |
Eric Strole
|
|
|
|
CHANGE STATUS TO (I) | | | 5/4/2016 | | DONE |
|
|
|
Reopen per Eric. Shouldn't have been closed
|
Final | 5/3/2016 | 5/3/2016 | 5/3/2016 | P | NH |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Todd Walter-no access
|
Plumbing Rough-in | 3/8/2016 | 3/8/2016 | 3/8/2016 | P | PASS |
Bill VanDegrift
|
|
|
Todd Phone #: ###-#### will fur out the garage behind the water lines to allow insulation between the water lines and the garage.
|
Plumbing Rough-in | 3/6/2016 | 3/7/2016 | 3/7/2016 | A | FAIL |
Bill VanDegrift
|
|
|
After talking with Bill, Water lines in garage wall and ceiling ok due to fact other side is heated space. I adjusted some to maximize insulation. We will be using heat tape under stairwell for exposed piping. I repiped drain piping to meet code for horizontal wet venting. Phone #: ###-#### Inspection requested via web by Todd Walter 1) waste test ok 2) raise water in garage ceiling above the insulation. 3) move water lines in garage wall to inside the insulation 4) call me to go over this when you and the builder can meet me on the job.
|
Plumbing Rough-in | 2/28/2016 | 2/29/2016 | 2/29/2016 | A | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Todd Walter-Need to run horizontal wet vent per the 2009 ISPC.Need to fix reverse grade on 3" at stairwell. Need to raise waterlines in garage overhead to prevent from freezing. Waterlines in stairwell wall need to be in the warm side of wall and need to protect waterlines under stairs from freezing.
|
Water and/or Sewer | 2/28/2016 | 2/29/2016 | 2/28/2016 | A | CANC |
Eric Strole
|
|
|
Phone #: ###-#### >> Inspection requested via web by Todd Walter Inspection cancelled from web by: Todd Walter
|
Issue PAID IN FULL permit | | | 2/28/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/28/2016 | | DONE |
|
|
|
This permit was created on the web by Todd Walter
|