Final | 3/23/2017 | 3/24/2017 | 3/24/2017 | A | PASS |
Dan Ediger
|
|
|
Dean Phone #: ###-####
|
Final | 3/23/2017 | 3/23/2017 | 3/23/2017 | P | FAIL |
Dan Ediger
|
|
|
Clint Phone #: ###-####-master bath. 1. Toilet requires a 2" vent. No vent present. 2. Dishwasher drain must rise to the top of the cabinet and drain down to the disposal. 3. Certify double check. 4. Install a combustion air inlet unrestricted into the attic at the fau. 40 sq in min.
|
PLM-Aging Inspection | 3/17/2017 | 3/17/2017 | 3/17/2017 | | PEND |
Bill VanDegrift
|
|
|
no calls
|
Plumbing Rough-in | 8/24/2016 | 8/24/2016 | 8/24/2016 | P | PART |
Bill VanDegrift
|
|
|
Dean Phone #: ###-#### partial ri ok, ok to rock, crawl not done yet.
|
Plumbing Rough-in | 8/23/2016 | 8/23/2016 | 8/23/2016 | P | FAIL |
Bill VanDegrift
|
|
|
Dean Phone #: ###-#### 1) lav waste arm backgraded. 2) needs nail plates 3) waste connection to a closet arm prohibited 4) repipe shower waste and vent to code compliance. left owner a drawing of the waste to refer to.
|
Issue PAID IN FULL permit | | | 8/23/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/23/2016 | | DONE |
|
|
|
This permit was created on the web by Dean Rooke
|