Final | 1/23/2018 | 1/23/2018 | 1/23/2018 | P | PASS |
Eric Strole
|
|
|
Unit 201. Roof drain covers Phone #: ###-#### Inspection requested via web by wes Ritchie
|
Final | 11/29/2017 | 11/29/2017 | 11/29/2017 | P | PART |
Eric Strole
|
|
|
Temp final ok. Unit 201 needs complete & need 2 baskets on roof drains.
|
Final | 11/29/2017 | 11/29/2017 | 11/29/2017 | P | CANC |
Eric Strole
|
|
|
411-201 threw 220 Phone #: ###-#### Inspection requested via web by wes Ritchie
|
Final | 11/27/2017 | 11/27/2017 | 11/27/2017 | A | PART |
Eric Strole
|
|
|
311 threw 320 411-412-415-417-418 Phone #: ###-#### Inspection requested via web by wes Ritchie-Units 311 thru 320, 412, 415, 417 & 418 pass.
|
Final | 11/24/2017 | 11/24/2017 | 11/24/2017 | P | PART |
Eric Strole
|
|
|
10-units on 5th 510-520 19-units on 4th 401-420 minus 411 18- units on 3rd 301-320 Minus 311 Phone #: ###-#### Inspection requested via web by wes Ritchie-Units 301 thru 310, 401 thru 409, 410, 413, 414, 416, 419, 420, 510 thru 520 pass.
|
Final | 11/8/2017 | 11/9/2017 | 11/9/2017 | A | PART |
Eric Strole
|
|
|
501 to 510 tower one floor five Phone #: ###-#### Inspection requested via web by wes Ritchie-Units 501 thru 510 pass.
|
Other | 10/5/2017 | 10/5/2017 | 10/5/2017 | A | PART |
Bill VanDegrift
|
|
|
Main water line building 2 Phone #: ###-#### Inspection requested via web by wes Ritchie water is on
|
Other | 8/22/2017 | 8/22/2017 | 8/22/2017 | P | PART |
Eric Strole
|
|
|
Water heater vents second floor Phone #: ###-#### Inspection requested via web by wes Ritchie-Test on water heater flues in units 212, 213, 214 & 220 pass.
|
Other | 8/21/2017 | 8/21/2017 | 8/21/2017 | P | PART |
Eric Strole
|
|
|
Water heater vents Phone #: ###-#### Inspection requested via web by wes Ritchie-Test on water heater flues in units 211 thru 216 pass.
|
Other | 8/15/2017 | 8/16/2017 | 8/16/2017 | A | PART |
Eric Strole
|
|
|
4-water heater vents on third floor Phone #: ###-#### Inspection requested via web by wes Ritchie-Test on water heater flues in units 312, 314, 316 & 318 pass.
|
Other | 8/15/2017 | 8/15/2017 | 8/15/2017 | A | PART |
Eric Strole
|
|
|
Water heater vents on third floor Phone #: ###-#### Inspection requested via web by wes Ritchie-Test on water heater flues in units 311, 313, 315, 317, 319 & 320 pass.
|
Other | 8/3/2017 | 8/3/2017 | 8/3/2017 | P | PART |
Eric Strole
|
|
|
4-water heater vents on fourth floor Phone #: ###-#### Inspection requested via web by wes Ritchie-Test on water heater flues in units 415, 418, 419 & 420 pass.
|
Other | 7/31/2017 | 7/31/2017 | 7/31/2017 | P | PASS |
Ben Livingston
|
|
|
Water heaters vents fourth floor Phone #: ###-#### Inspection requested via web by wes Ritchie 5lb flue rooms 411,412,413,414,416,417
|
Other | 7/24/2017 | 7/24/2017 | 7/24/2017 | P | PART |
Eric Strole
|
|
|
Water heater vents 5th floor Phone #: ###-#### Inspection requested via web by wes Ritchie-test on w/h flues in units 511, 512 & 518 pass
|
Other | 7/20/2017 | 7/20/2017 | 7/20/2017 | P | PART |
Eric Strole
|
|
|
Water heater vents Phone #: ###-#### Inspection requested via web by wes Ritchie-Test on w/h flues units 513 thru 519 pass.
|
Other | 6/28/2017 | 6/29/2017 | 6/29/2017 | A | PART |
Eric Strole
|
|
|
203 204 water heater vents Inspection requested via web by wes Ritchie-Water heater flues units 203 & 204 pass.
|
Other | 6/19/2017 | 6/20/2017 | 6/20/2017 | P | PART |
Eric Strole
|
|
|
Water heater vents Inspection requested via web by wes Ritchie-Test on water heater flues in units 202, 205 & 206 pass.
|
Other | 6/19/2017 | 6/19/2017 | 6/19/2017 | A | PART |
Eric Strole
|
|
|
Water heater vents Inspection requested via web by wes RitchieTest on w/h flues in units 201, 207, 208, 209, 210 pass.
|
Plumbing Rough-in | 6/13/2017 | 6/13/2017 | 6/13/2017 | P | PART |
Daryl Spivey
|
|
|
Water pipe on fifth floor. Water heater vents on third floor Phone #: ###-#### Inspection requested via web by wes Ritchie water heater vents rms 300, 302, 310 and 309 tested and water on 5th floor all tested ok...........ds
|
Roof Drains | 6/12/2017 | 6/12/2017 | 6/12/2017 | P | PASS |
Daryl Spivey
|
|
|
Roof and overflow drain Inspection requested via web by wes Ritchie bld 2 roof drains tested ok..........ds
|
Roof Drains | 6/7/2017 | 6/8/2017 | 6/8/2017 | P | PART |
Eric Strole
|
|
|
4throof drains and water heater vents Inspection requested via web by wes Ritchie-Test on water heater flues in rooms 302 thru 308 pass.
|
Plumbing Rough-in | 6/8/2017 | 6/8/2017 | 6/8/2017 | A | PART |
Eric Strole
|
|
|
4th. Floor waters garage vent test dwv to unit 412 Inspection requested via web by wes Ritchie-East tower DWV pass. 4" vent for garage drains pass. 4th flr test on water east tower pass. Test on water heater flue room 412 pass.
|
Water and/or Sewer | 6/7/2017 | 6/8/2017 | 6/8/2017 | A | CANC |
Eric Strole
|
|
|
4th. Floor waters garage vent test dwv to unit 412 Inspection requested via web by wes Ritchie
|
Other | 6/6/2017 | 6/6/2017 | 6/6/2017 | P | PART |
Eric Strole
|
|
|
Gas piping. Some dwv Inspection requested via web by wes Ritchie-East tower 60 lb gas tests pass. Can only have 24 fixture units on a 2" vent. Need to fix leak on DWV.
|
Other | 5/30/2017 | 5/30/2017 | 5/30/2017 | P | PART |
Eric Strole
|
|
|
Water heater vents Inspection requested via web by wes Ritchie-Test on w/h flues in units 412, 404, 406, 408 pass
|
Other | 5/24/2017 | 5/24/2017 | 5/24/2017 | P | PASS |
Ben Livingston
|
|
|
Gas on half of east tower. One water heater vent on five four on forth floor Inspection requested via web by wes Ritchie 21 60lb test east tower, 502,403,405,407,409 5lb flue
|
Plumbing Rough-in | 5/17/2017 | 5/18/2017 | 5/18/2017 | A | PART |
Eric Strole
|
|
|
Inspection requested via web by wes Ritchie-1st & 2nd flr east tower test on dwv pass.
|
Plumbing Rough-in | 5/17/2017 | 5/17/2017 | 5/17/2017 | P | PART |
Eric Strole
|
|
|
Water line third floor Inspection requested via web by wes Ritchie-3rd flr test on water east tower pass.
|
Other | 5/15/2017 | 5/15/2017 | 5/15/2017 | P | PART |
Eric Strole
|
|
|
Four water heater vents on fifth floor west tower Inspection requested via web by wes Ritchie-Units 504 thru 510 test on water heater flues pass.
|
Plumbing Rough-in | 5/11/2017 | 5/11/2017 | 5/11/2017 | P | PART |
Eric Strole
|
|
|
Inspection requested via web by wes Ritchie-Need to fix leaks and reverse grade and missing nailplates and need to be 6" above flood level rim before tieing vents together.
|
Other | 5/9/2017 | 5/10/2017 | 5/10/2017 | A | PART |
Eric Strole
|
|
|
4 water heater vents Inspection requested via web by wes Ritchie-Test on water heater flues in units 501 thru 509 pass.
|
Plumbing Rough-in | 5/2/2017 | 5/3/2017 | 5/3/2017 | A | PART |
Eric Strole
|
|
|
East tower garage dwv Seconded floor dwv waters on second floor Inspection requested via web by wes Ritchie-2nd flr east tower test on water in units pass.
|
Plumbing Rough-in | 4/24/2017 | 4/24/2017 | 4/24/2017 | P | PART |
Eric Strole
|
|
|
Inspection requested via web by wes Ritchie-Water in units 2nd flr west tower pass.
|
Plumbing Rough-in | 4/17/2017 | 4/18/2017 | 4/18/2017 | P | PART |
Eric Strole
|
|
|
DWV 2nd & 3rd flr west tower pass.
|
Plumbing Rough-in | 4/17/2017 | 4/17/2017 | 4/18/2017 | P | PART |
Bill VanDegrift
|
|
|
waste test only 3rd floor, leak on santee room 308
|
Plumbing Rough-in | 4/17/2017 | 4/17/2017 | 4/17/2017 | P | PART |
Eric Strole
|
|
|
Need to fix 3 leaks on dwv 2nd flr west tower.
|
Plumbing Rough-in | 4/13/2017 | 4/13/2017 | 4/13/2017 | A | PART |
Eric Strole
|
|
|
Water pipe on third floor Inspection requested via web by wes Ritchie-Test on water 3rd flr west tower pass.
|
Plumbing Rough-in | 4/11/2017 | 4/11/2017 | 4/11/2017 | P | PASS |
Eric Strole
|
|
|
Inspection requested via web by wes Ritchie-Primary and secondary roof drains west tower pass.
|
Plumbing Rough-in | 4/10/2017 | 4/10/2017 | 4/10/2017 | P | CANC |
Eric Strole
|
|
|
>> Inspection requested via web by wes Ritchie Inspection cancelled from web by: wes Ritchie
|
Plumbing Rough-in | 4/7/2017 | 4/10/2017 | 4/10/2017 | A | CANC |
Eric Strole
|
|
|
|
Other | 4/7/2017 | 4/7/2017 | 4/7/2017 | P | PART |
Eric Strole
|
|
|
West tower all 60 lb gas test pass.
|
Plumbing Rough-in | 4/6/2017 | 4/7/2017 | 4/7/2017 | P | NR |
Eric Strole
|
|
|
|
Other | 4/6/2017 | 4/7/2017 | 4/7/2017 | A | PART |
Eric Strole
|
|
|
60 lb gas test on 9 units west tower pass
|
Other | 4/6/2017 | 4/6/2017 | 4/6/2017 | P | PART |
Eric Strole
|
|
|
Water on 4 th Gas on 2and 3 Inspection requested via web by wes Ritchie-60 lb gas test on 9 units west tower pass.
|
Plumbing Rough-in | 4/6/2017 | 4/6/2017 | 4/6/2017 | P | PART |
Eric Strole
|
|
|
Water on 4 th Gas on 2and 3 Inspection requested via web by wes Ritchie-Test on water 4th flr west tower pass.
|
Other | 3/31/2017 | 3/31/2017 | 3/31/2017 | P | PART |
Eric Strole
|
|
|
Gas line inspection Phone #: ###-#### Inspection requested via web by wes Ritchie-60 lb gas test west tower pass. 10 units.
|
Roof Drains | 3/29/2017 | 3/30/2017 | 3/30/2017 | P | CANC |
Eric Strole
|
|
|
Inspection cancelled from web by: wes Ritchie
|
Plumbing Rough-in | 3/29/2017 | 3/29/2017 | 3/29/2017 | P | PART |
Eric Strole
|
|
|
Dwv on fifth floor ten units Phone #: ###-#### Inspection requested via web by wes Ritchie-DWV test west tower 4th & 5th flr pass.
|
Other | 3/29/2017 | 3/29/2017 | 3/29/2017 | P | PART |
Eric Strole
|
|
|
Gas on fifth floor Phone #: ###-#### Inspection requested via web by wes Ritchie-60 lb gas test 5th flr west tower pass. 10 units.
|
Plumbing Rough-in | 3/24/2017 | 3/24/2017 | 3/24/2017 | P | PART |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by wes Ritchie-Water 5th flr tower 5 pass.
|
Water and/or Sewer | 3/24/2017 | 3/24/2017 | 3/24/2017 | P | CANC |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by wes Ritchie
|
PLM-Aging Inspection | 3/22/2017 | 3/22/2017 | 3/22/2017 | | PART |
Eric Strole
|
|
|
wip
|
Issue PAID IN FULL permit | | | 8/30/2016 | | |
|
|
|
|
Application received | | | 8/23/2016 | | DONE |
|
|
|
This permit was created on the web by wes Ritchie
|
First Notice | 1/23/2018 | 1/23/2018 | | | |
Eric Strole
|
|
|
|