Water and/or Sewer | 1/26/2017 | 1/26/2017 | 1/26/2017 | P | CANC |
Bill VanDegrift
|
|
|
|
Water and/or Sewer | 1/26/2017 | 1/26/2017 | 1/26/2017 | P | PASS |
Dan Ediger
|
|
|
|
DOC - Permit Finaled | 1/26/2017 | 1/26/2017 | 1/26/2017 | P | PASS |
Dan Ediger
|
|
|
|
Water and/or Sewer | 1/20/2017 | 1/23/2017 | 1/23/2017 | A | CANC |
Dan Ediger
|
|
|
Victor Phone #: ###-####
|
Water and/or Sewer | 1/20/2017 | 1/20/2017 | 1/20/2017 | P | PART |
Dan Ediger
|
|
|
Sewer OK. Leave the joints in the water service exposed until it is tested. Could not find the water meter under the snow. Will call for inspection when they locate the water meter.
|
Water and/or Sewer | 1/17/2017 | 1/18/2017 | 1/18/2017 | A | FAIL |
Dan Ediger
|
|
|
victor Phone #: ###-#### 1. Install a tracer wire on the water service per ISPC 604.8. 2. Test the water service with 50 psi air or water. 3. Test the sewer with 5 psi air pressure or fill with water. 4. Install Schedule 40 pipe 3 feet from the house into the crawl space. 5. Install a schedule 40 wye branch fitting for the sewer cleanout. A santiary tee is not acceptable. 6. The gasketed 3034 sewer pipe is installed backwards. The female hub must be downstream of the male pipe. See drawing on the correction notice.
|
Application received | | | 1/17/2017 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 1/17/2017 | | DONE |
|
|
|
|