First Notice | 12/12/2017 | 12/12/2017 | 6/1/2018 | | DONE |
Dan Ediger
|
|
|
This permit finaled on the web by David or K Cole
|
Final | 12/5/2017 | 12/12/2017 | 12/12/2017 | P | PASS |
Dan Ediger
|
|
|
Please call the Tenant, Barbara at ###-#### in Unit #103 with a 30 minute heads up arrival time. Thank you. Phone #: ###-#### Inspection requested via web by David or K Cole
|
PLM-Aging Inspection | 11/21/2017 | 11/21/2017 | 11/22/2017 | | PEND |
Dan Ediger
|
|
|
Contractor to schedule
|
PLM-Aging Inspection | 8/22/2017 | 8/22/2017 | 8/23/2017 | | PEND |
Dan Ediger
|
|
|
Contractor to complete and schedule
|
Water and/or Sewer | 1/24/2017 | 1/24/2017 | 1/24/2017 | P | CANC |
Dan Ediger
|
|
|
|
Water Heater Final | 1/24/2017 | 1/24/2017 | 1/24/2017 | P | FAIL |
Dan Ediger
|
|
|
1. Center the water heater in the pan. 2. The wh must have 2" clearance around the whole water heater. 3. Install the supplied burner filter around the base of the water heater. 4. Clean the combustioin air register next to the water heater. 5. Pipe the wh drain pan to the outside. Cannot terminate in the crawl space.
|
Water Heater Final | 1/23/2017 | 1/24/2017 | 1/24/2017 | P | NH |
Dan Ediger
|
|
|
Please call the Tenant, Barb at ###-#### with a 30 minute heads up arrival time. Phone #: ###-#### Inspection requested via web by David or K Cole. Left phone message and tagged the door
|
Issue PAID IN FULL permit | | | 1/23/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/23/2017 | | DONE |
|
|
|
This permit was created on the web by David or K Cole
|