Final | 6/26/2018 | 6/27/2018 | 6/27/2018 | A | PASS |
Dan Ediger
|
|
|
Cindy Phone #: ###-####
|
Water Heater Final | 6/20/2018 | 6/21/2018 | 6/21/2018 | A | FAIL |
Dan Ediger
|
|
|
Cindy-please call when on way Phone #: ###-####. The plastic pan must be completley removed from under the gas water heater.
|
PLM-Aging Inspection | 5/7/2018 | 5/7/2018 | 5/10/2018 | | PEND |
Dan Ediger
|
|
|
Met with the homeowner. She will remove the plastic pan and run the t&p with approved material.
|
PLM-Aging Inspection | 2/5/2018 | 2/5/2018 | 2/5/2018 | | PEND |
Bill VanDegrift
|
|
|
no calls
|
PLM-Aging Inspection | 11/6/2017 | 11/6/2017 | 11/7/2017 | | PEND |
Dan Ediger
|
|
|
|
Water and/or Sewer | 4/26/2017 | 4/26/2017 | 4/26/2017 | P | FAIL |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by Cindy Wilcox. Use a metal drain pan on the gas water heater. Use a code approved material on the t&p drain. CPVC, copper or galvanized pipe.
|
Issue PAID IN FULL permit | | | 4/26/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/26/2017 | | DONE |
|
|
|
This permit was created on the web by Cindy Wilcox
|