Print Statement | | | 10/5/2017 | | DONE |
|
|
|
|
Final | 7/31/2017 | 8/1/2017 | 8/1/2017 | P | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Travis Baker
|
Final | 7/31/2017 | 7/31/2017 | 7/31/2017 | P | PART |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by Travis Baker. Add a thermostatic valve to the existing bath so both lavatory sinks are protected
|
Final | 7/14/2017 | 7/14/2017 | 7/14/2017 | P | PART |
Dan Ediger
|
|
|
Mop sink plumbing ok to cover. Temp occ approved for plumbing
|
Final | 7/13/2017 | 7/14/2017 | 7/14/2017 | A | NR |
Dan Ediger
|
|
|
Requesting a temporary occupancy for the plumbing Phone #: ###-#### Inspection requested via web by Travis Baker
|
Final | 7/12/2017 | 7/13/2017 | 7/13/2017 | A | FAIL |
Dan Ediger
|
|
|
Tenant is requesting to get a temp cert of occupancy until the counter tops come in. I have a break room sink that needs to be set. Phone #: ###-#### Inspection requested via web by. Travis Baker. 1. Add a double check valve to the water service. 2. Install an expansion tank at the water heater. 3. Pipe the t&p with approved material. 4. Install a tempering valve to the restroom sinks or one at the water heater.
|
Plumbing Rough-in | 6/8/2017 | 6/9/2017 | 6/9/2017 | A | PASS |
Bill VanDegrift
|
|
|
If door is locked Please call Travis at ###-#### for the code to the lock box on the front door. Phone #: ###-#### Inspection requested via web by Travis Baker ri ok
|
Issue PAID IN FULL permit | | | 6/8/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/8/2017 | | DONE |
|
|
|
This permit was created on the web by Travis Baker
|
First Notice | 8/1/2017 | 8/1/2017 | | | |
Eric Strole
|
|
|
|