Final | 10/25/2017 | 10/26/2017 | 10/26/2017 | A | PASS |
Dan Ediger
|
|
|
Lock box code 6021. Lock box is located on the garage back door. Phone #: ###-#### Inspection requested via web by Ryan Baker
|
Plumbing Rough-in | 8/9/2017 | 8/10/2017 | 8/10/2017 | A | PASS |
Dan Ediger
|
|
|
6021 lock box code Phone #: ###-#### Inspection requested via web by Ryan Baker
|
Plumbing Rough-in | 8/8/2017 | 8/9/2017 | 8/9/2017 | A | FAIL |
Dan Ediger
|
|
|
lock box code 6021 Inspection requested via web by Ryan Baker. Kitchen sink drain is flat. Missing nail plates at the 3" stack base and in the shouwer.
|
Plumbing Rough-in | 8/7/2017 | 8/8/2017 | 8/8/2017 | A | FAIL |
Dan Ediger
|
|
|
lock box code is in the back of the house on the garage door.. the code is 6021 Phone #: ###-#### Inspection requested via web by Ryan Baker. 1. Support 2" vent at 48" . 2. The lavatory trap arm is flat and is too long. Max 36" in the wall. 3. Missing several nail plates. 4. The shower diverter is crooked. Straighten out so it can be sealed on trim. 5. The kitchen sink drain is flat.
|
Issue PAID IN FULL permit | | | 7/24/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/24/2017 | | DONE |
|
|
|
This permit was created on the web by Ryan Baker
|