Final | 6/11/2018 | 6/12/2018 | 6/12/2018 | A | PASS |
Daryl Spivey
|
|
|
Phone #: ###-#### Inspection requested via web by Guy Davis
|
PLM-Aging Inspection | 6/8/2018 | 6/8/2018 | 6/8/2018 | | PEND |
Daryl Spivey
|
|
|
wip
|
Plumbing Rough-in | 11/28/2017 | 11/29/2017 | 11/29/2017 | A | PASS |
Daryl Spivey
|
|
|
Phone #: ###-#### Inspection requested via web by Guy Davis
|
Groundwork | 9/22/2017 | 9/25/2017 | 9/25/2017 | A | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Guy Davis
|
Issue PAID IN FULL permit | | | 9/22/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/22/2017 | | DONE |
|
|
|
This permit was created on the web by Guy Davis
|