Final | 3/9/2018 | 3/9/2018 | 3/9/2018 | P | PASS |
Dan Ediger
|
|
|
Please call when you are on the way so we can meet you there Phone #: ###-#### Inspection requested via web by Dan McFate
|
Final | 2/28/2018 | 3/1/2018 | 3/1/2018 | P | FAIL |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by Dan McFate. 1. The condensate drain must be run or pumped to an approved drain. Will freeze outside. 2. You cannont use flex connectors to pipe to the water heater. Only one 24" max. to connect heater on each side. 3. Provide a bug screen on the air inlet. 4. The flue must be panited per code.
|
Issue PAID IN FULL permit | | | 12/28/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Telephone call | | | 12/28/2017 | | DONE |
|
|
|
called again-left message asking them to call us-need to know if they want us to void permit
|
Telephone call | | | 11/28/2017 | | DONE |
|
|
|
Spoke with Debra to see if this project is happening since it hasn't been paid for or issued. she stated she will check with the receptionist when back from lunch and will call be back
|
Telephone call | | | 11/2/2017 | | DONE |
|
|
|
Left another message to see if this permit is going to be paid for so it can be issued or if it needs to be voided
|
Telephone call | | | 10/13/2017 | | DONE |
|
|
|
Left a message for Dan to see if this permit is going to be paid for or if it needs to be voided
|
Application received | | | 9/26/2017 | | DONE |
|
|
|
This permit was created on the web by Dan McFate
|
First Notice | 3/9/2018 | 3/9/2018 | | | |
Dan Ediger
|
|
|
|