Final | 2/10/2018 | 2/12/2018 | 2/12/2018 | A | PASS |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Pherigo units 15-20 ok
|
Final | 2/9/2018 | 2/9/2018 | 2/9/2018 | P | FAIL |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by Troy Pherigo. Only one slip joint on the outlet side of the trap. Strap all dishwasher hose up as high as possible under the ks.
|
Plumbing Rough-in | 10/24/2017 | 10/24/2017 | 10/24/2017 | P | PASS |
Dan Ediger
|
|
|
Troy Pherigo-Re-inspection Phone #: ###-#### Inspection requested via web by Troy Pherigo
|
Plumbing Rough-in | 10/18/2017 | 10/18/2017 | 10/18/2017 | P | FAIL |
Dan Ediger
|
|
|
Building unlocked Troy Pherigo-###-#### Phone #: ###-#### Inspection requested via web by Troy Pherigo. Water heaters: a. Remove flex connectors from all six water t&p valves and hard pipe full size to within 6" to 18" of grade. b. Pipe water heater drain pipes on all six units a minimum of 3/4" to an approved location.
|
Issue PAID IN FULL permit | | | 10/18/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/18/2017 | | DONE |
|
|
|
This permit was created on the web by Troy Pherigo
|
First Notice | 2/12/2018 | 2/12/2018 | | | |
Dan Ediger
|
|
|
|