PLM-Aging Inspection | 8/22/2018 | 8/22/2018 | 8/27/2018 | | PASS |
Dan Ediger
|
|
|
|
DOC - Permit Expired | 8/27/2018 | 8/27/2018 | 8/27/2018 | A | PASS |
Dan Ediger
|
|
|
the homeowner will not adhear to the correction notice. Plans on moving the water heater to the garage.
|
Final | 12/11/2017 | 12/12/2017 | 12/12/2017 | A | PART |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette. Water heater ok. homeowner is installing self closing door and gaskets
|
Final | 11/28/2017 | 11/30/2017 | 11/30/2017 | A | FAIL |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette. The water heater is in the master bathroom closet. 1. The closet door must be self-closer and gasketed. NFPA 80.6.1.4.2 2. The water heater pan is covering the lower combustion air. Cut a new combustion air opening to meet code. 3. The T&P is trapped and you cannot connect with a flex. Remove the flex an pipe without being trapped.
|
Issue PAID IN FULL permit | | | 11/22/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/22/2017 | | DONE |
|
|
|
This permit was created on the web by Mary LaFayette
|