Final | 2/24/2019 | 2/25/2019 | 2/25/2019 | P | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Jeffrey Hankins
|
Card not on site to sign | 2/25/2019 | 2/25/2019 | 2/25/2019 | P | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Jeffrey Hankins
|
Fees Due Hold | 2/23/2019 | | 2/24/2019 | | DONE |
|
|
|
|
Final | 2/21/2019 | 2/22/2019 | 2/22/2019 | A | FAIL |
Eric Strole
|
|
|
Inspection requested via web by Jeffrey Hankins-Drain for RPBA for premis protection needs to terminate above grade. Reinspection fee issued.
|
Final | 2/18/2019 | 2/19/2019 | 2/19/2019 | A | FAIL |
Matt Wrobel
|
|
|
Phone #: ###-#### Inspection requested via web by Jeffrey Hankins provide adequate drainage for RPBA or install DBCA all backflow devices need to be certified
|
Final | 2/13/2019 | 2/15/2019 | 2/15/2019 | A | FAIL |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Jeffrey Hankins-Need to install a DBCA on water supply for premis protection. Need to install a RPBA on carbonator for soda. Need to install a RPBA on dishwasher. Need to caulk mop sink. Need to use approved material for T&P. Cannot tie T&P and condensate for water heater together. Cannot have pex within 18" of a water heater connection. Need a seperate shutoff valve for water heater.
|
PLM-Aging Inspection | 12/20/2018 | 12/20/2018 | 12/20/2018 | | PART |
Eric Strole
|
|
|
No calls
|
Plumbing Rough-in | 9/20/2018 | 9/21/2018 | 9/21/2018 | A | PASS |
Eric Strole
|
|
|
Phone #: ###-#### Inspection requested via web by Jeffrey Hankins
|
Plumbing Rough-in | 8/23/2018 | 8/27/2018 | 8/27/2018 | A | FAIL |
Eric Strole
|
|
|
Inspection requested via web by Jeffrey Hankins-Grease trap is undersized per the approved plans. Grease trap is required to have a 3" drain and floor sink. Grease trap is required to have a flow control with a vent. Flow control needs to be accessible. Cannot have a waterline in a 2x4 exterior wall.
|
Plumbing Rough-in | 8/23/2018 | 8/27/2018 | 8/23/2018 | P | CANC |
Eric Strole
|
|
|
>> Inspection requested via web by Jeffrey Hankins Inspection cancelled from web by: Jeffrey Hankins
|
Groundwork | 5/3/2018 | 5/4/2018 | 5/4/2018 | P | PASS |
Eric Strole
|
|
|
door code for entrance 67801 Phone #: ###-#### Inspection requested via web by Jeffrey Hankins
|
(F) Reprint permit | | | 3/27/2018 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 1/24/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Telephone call | | | 1/24/2018 | | DONE |
|
|
|
called to let know building permit has not been issued yet so no work should be done yet. Once the building permit has been issued, they may be started
|
Owner Supplied Equipment | | | 1/23/2018 | | |
|
|
|
|
Application received | | | 1/23/2018 | | DONE |
|
|
|
This permit was created on the web by Jeffrey Hankins
|
First Notice | 2/25/2019 | 2/25/2019 | | | |
Eric Strole
|
|
|
|