Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberPLM18-01124
StatusFinaled
Name ALL STAR PLUMBING
Site Address 8011 W FAIRVIEW AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Run (2) new water lines and (2) double checks for new service.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/21/20183/21/20183/21/2018PPASS
DetailsDan Ediger
Please call Tyler with questions ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Jennifer Alcala
Water and/or Sewer3/20/20183/20/20183/20/2018PFAIL
DetailsDan Ediger
Please call Johnny with questions ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Jennifer Alcala.
1. The Zurn 950xl isn't approved for vertical installation. Change to an assembly approved for vertical or install in the horizontal.
2. Certifiy all dobule check valves including the one for the sprinklers.
3. Install shut-off valves for each unit.
4 Replace the defective expansion tank in the Tennis shop.
Issue PAID IN FULL permit  3/20/2018 DONE
Payment received via Govolutions
Owner Supplied Equipment  3/20/2018  
Application received  3/20/2018 DONE
This permit was created on the web by Jennifer Alcala
First Notice3/21/20183/21/2018   
DetailsDan Ediger