DOC - Permit Finaled | 3/23/2018 | 3/23/2018 | 3/23/2018 | P | PASS |
Dan Ediger
|
|
|
complete
|
Final | 3/22/2018 | 3/22/2018 | 3/22/2018 | P | CANC |
Dan Ediger
|
|
|
Made corrections as noted Phone #: ###-#### Inspection requested via web by Cesar Rodriguez. Install a loop in the condensate drain off the flue per manufacturers instructions. Loop tubing, send me a picture and schedule inspection.
|
Final | 3/21/2018 | 3/21/2018 | 3/21/2018 | P | FAIL |
Brian Scoles
|
|
|
Replaced waterheater. Homeowner is Allen Tudor ###-#### Thank You Phone #: ###-#### Inspection requested via web by Cesar Rodriguez- T&P need to be routed to garage floor not into pan under water heater- need to install drip leg on gas line between shutoff and appliance- need to provide CO detectors
|
Issue PAID IN FULL permit | | | 3/21/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/21/2018 | | DONE |
|
|
|
This permit was created on the web by Cesar Rodriguez
|