Final | 7/2/2018 | 7/3/2018 | 7/3/2018 | A | PASS |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by TOBI WLSON
|
Final | 6/28/2018 | 6/29/2018 | 6/29/2018 | P | FAIL |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by TOBI WLSON. 1. The expansion tank is isolated from the water heater by the check valve. Install the e.t. on the wh side of the check. 2. Cell core pipe cannot be used on the water heater flue, only air intake side.
|
Plumbing Rough-in | 4/13/2018 | 4/16/2018 | 4/16/2018 | A | PASS |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by TOBI WLSON
|
Groundwork | 3/30/2018 | 4/2/2018 | 4/2/2018 | A | PASS |
Dan Ediger
|
|
|
Please call Sam Collier with any questions ###-#### Phone #: ###-#### Inspection requested via web by TOBI WLSON
|
Issue PAID IN FULL permit | | | 3/26/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/26/2018 | | DONE |
|
|
|
This permit was created on the web by TOBI WLSON
|
First Notice | 7/3/2018 | 7/3/2018 | | | |
Dan Ediger
|
|
|
|