VOIDED CHANGE STATUS | | | 7/12/2018 | | DONE |
|
|
|
as per McKenna-she said after talking to the inspector Dan Ediger tah they hsould void this permit and use the existing one that never had an inspection but some company did the work- See PLM17-03715
|
Final | 6/29/2018 | 7/2/2018 | 7/2/2018 | A | FAIL |
Dan Ediger
|
|
|
Backflow was tested and passed by Pacific Backflow. Phone #: ###-#### Inspection requested via web by McKenna Haycock. 1. The double check valve is not an approved backflow assembly for irrigation per ISPC. Any backflow assembly that is changed out must be brought up to code. 2. PVC male fitting must be a minimum of schedule 80. ISPC 605.12.3
|
Issue PAID IN FULL permit | | | 6/26/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/26/2018 | | DONE |
|
|
|
This permit was created on the web by McKenna Haycock
|