Final | 2/14/2019 | 2/15/2019 | 2/15/2019 | A | PASS |
Matt Wrobel
|
|
|
Garage code 6175 Phone #: ###-#### Inspection requested via web by Erin Whiting
|
Plumbing Rough-in | 11/5/2018 | 11/6/2018 | 11/6/2018 | P | PASS |
Matt Wrobel
|
|
|
Phone #: ###-#### Inspection requested via web by Erin Whiting
|
Plumbing Rough-in | 10/30/2018 | 10/31/2018 | 10/31/2018 | A | FAIL |
Dan Ediger
|
|
|
Phone #: ###-#### Inspection requested via web by Erin Whiting 1. strap vents at 4 foot spacing,-2. water closes too close to tum 15" minimun. 3. bring 3" cleanouts for both baths above floor or within 5 feet of crawl. 4. cleanouts must have 24" clear not behind w.c. facing bowl. 5. missing nailplates. 6. hot water lines below conditioned space to be insulated per energy code
|
Issue PAID IN FULL permit | | | 9/24/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/24/2018 | | DONE |
|
|
|
This permit was created on the web by Erin Whiting
|