PLM-Aging Inspection | 7/16/2020 | 7/16/2020 | 7/16/2020 | | PART |
Eric Strole
|
|
|
No calls
|
PLM-Aging Inspection | 4/16/2020 | 4/16/2020 | 4/16/2020 | | PART |
Eric Strole
|
|
|
No calls
|
PLM-Aging Inspection | 1/16/2020 | 1/16/2020 | 1/16/2020 | | PART |
Eric Strole
|
|
|
No calls
|
PLM-Aging Inspection | 10/17/2019 | 10/17/2019 | 10/17/2019 | | PASS |
Daryl Spivey
|
|
|
|
Plumbing Rough-in | 7/18/2019 | 7/18/2019 | 7/18/2019 | P | PASS |
Eric Strole
|
|
|
Shower value installed. Need it inspected. Please call Bill at ###-####. So he can let you in. Phone #: ###-#### Inspection requested via web by Vance Poulsen
|
Plumbing Rough-in | 3/13/2019 | 3/14/2019 | 3/14/2019 | P | PASS |
Eric Strole
|
|
|
Please call Bill on your way out. ###-#### Phone #: ###-#### Inspection requested via web by Vance Poulsen
|
Plumbing Rough-in | 2/5/2019 | 2/5/2019 | 2/5/2019 | P | FAIL |
Eric Strole
|
|
|
Please contact Bill on your way out. ###-#### Use side gate on south side of house. Phone #: ###-#### Inspection requested via web by Vance Poulsen-Need to test DWV. Need to tent waterline in attic space. Cannot s-trap shower. Cross santee for vent installed in wrong direction. Santees are not approved for drainage in the horizontal. Need to vent toilet & shower per the 2017 ISPC. Need 3" base of stack cleanout. Need to be 6" above flood level rim before tieing horizontal vents together. Traps for wash basins need to be same size as trap arms.
|
Water and/or Sewer | 2/5/2019 | 2/5/2019 | 2/5/2019 | P | CANC |
Eric Strole
|
|
|
Please contact Bill on your way out. ###-#### Use side gate on south side of house. Phone #: ###-#### Inspection requested via web by Vance Poulsen
|
Issue PAID IN FULL permit | | | 2/5/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/5/2019 | | DONE |
|
|
|
This permit was created on the web by Vance Poulsen
|