First Notice | 10/22/2019 | 10/22/2019 | 7/27/2020 | | DONE |
Daryl Spivey
|
|
|
This permit finaled on the web by RM Mechanical
|
Final | 10/21/2019 | 10/22/2019 | 10/22/2019 | P | PASS |
Daryl Spivey
|
|
|
D18-063. tempering valves on the hot water for the L-2 fixtures in the public restroom Phone #: ###-#### Inspection requested via web by RM Mechanical
|
Final | 10/18/2019 | 10/21/2019 | 10/21/2019 | P | PART |
Daryl Spivey
|
|
|
D18-063 St Lukes Final Plumbing Inspection Phone #: ###-#### Inspection requested via web by RM Mechanical need tempering devices on public lavs and labeling in basement mech rm............ds
|
Groundwork | 8/29/2019 | 8/29/2019 | 8/29/2019 | P | PART |
Daryl Spivey
|
|
|
SB2 Underground plumbing waste and vent Phone #: ###-#### Inspection requested via web by RM Mechanical sanitary marked on plan................ds
|
Plumbing Rough-in | 8/14/2019 | 8/14/2019 | 8/14/2019 | P | CANC |
Daryl Spivey
|
|
|
partial rough in for the above ground water Phone #: ###-#### Inspection requested via web by RM Mechanical RO water..........ds
|
Plumbing Rough-in | 8/5/2019 | 8/7/2019 | 8/7/2019 | A | CANC |
Daryl Spivey
|
|
|
plumbing rough-in inspection for med gas in operating rooms Phone #: ###-#### Inspection requested via web by RM Mechanical
|
Med/Gas Systems | 8/7/2019 | 8/7/2019 | 8/7/2019 | A | PASS |
Daryl Spivey
|
|
|
plumbing rough-in inspection for med gas in operating rooms Phone #: ###-#### Inspection requested via web by RM Mechanical tie in to surgery room booms...........ds
|
Plumbing Rough-in | 8/5/2019 | 8/6/2019 | 8/5/2019 | A | CANC |
Daryl Spivey
|
|
|
rough-in inspection for med gas in operating rooms Phone #: ###-#### >> Inspection requested via web by RM Mechanical Inspection cancelled from web by: RM Mechanical
|
Other | 7/18/2019 | 7/19/2019 | 7/19/2019 | P | PART |
Daryl Spivey
|
|
|
Overhead Plumbing inspection for Central Sterile and Decontamination Phone #: ###-#### Inspection requested via web by RM Mechanical test ok....1st floor rough ins complete............ds
|
Med/Gas Systems | 7/8/2019 | 7/9/2019 | 7/9/2019 | A | PART |
Daryl Spivey
|
|
|
plumbing med gas inspection for Area B Phone #: ###-#### Inspection requested via web by RM Mechanical area B 24 hr test ok..........ds
|
Med/Gas Systems | 7/3/2019 | 7/8/2019 | 7/8/2019 | A | PART |
Eric Strole
|
|
|
plumbing med gas inspection for Area B Phone #: ###-#### Inspection requested via web by RM Mechanical-Start of 24 hr test on med gas.
|
Med/Gas Systems | 6/13/2019 | 6/14/2019 | 6/14/2019 | A | PART |
Daryl Spivey
|
|
|
Phone #: ###-#### Inspection requested via web by RM Mechanical 8 rooms east side tested out of walls...........ds
|
Plumbing Rough-in | 6/12/2019 | 6/12/2019 | 6/12/2019 | A | PART |
Daryl Spivey
|
|
|
Josh Wilson waste and vent and water in area B tested ok..........ds
|
Med/Gas Systems | 6/12/2019 | 6/12/2019 | 6/12/2019 | A | PART |
Daryl Spivey
|
|
|
Josh Wilson 5 rooms partial ok out of walls..start 24 hr test.......ds
|
Other | 6/11/2019 | 6/12/2019 | 6/12/2019 | P | PASS |
Daryl Spivey
|
|
|
We would like to schedule an inspection for the sewer waste and vent. Josh Wilson is the site contact ###-####. Please call before arriving. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical
|
Water and/or Sewer | 6/11/2019 | 6/12/2019 | 6/12/2019 | P | CANC |
Daryl Spivey
|
|
|
We would like to schedule an inspection on the domestic water system. Josh Wilson is the site contact ###-####. Please call before arriving. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical
|
Med/Gas Systems | 6/11/2019 | 6/12/2019 | 6/12/2019 | P | CANC |
Daryl Spivey
|
|
|
We would like to schedule a partial med gas inspection for Wednesday afternoon. Josh Wilson is the site contact ###-####. Please call before arriving. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical
|
Plumbing Rough-in | 6/7/2019 | 6/7/2019 | 6/7/2019 | P | PART |
Daryl Spivey
|
|
|
We would like to schedule a partial wall rough-in in the Central Sterile at St. Luke''s Surgery Center. Josh Wilson is the site contact ###-####, please contact him in advance. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical water test in central sterilization area...........ds
|
PLM-Aging Inspection | 6/6/2019 | 6/7/2019 | 6/7/2019 | P | CANC |
Daryl Spivey
|
|
|
We would like to schedule a partial wall rough-in in the Central Sterile at St. Luke''s Surgery Center. Josh Wilson is the site contact ###-####, please contact him in advance. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical
|
Other | 6/6/2019 | 6/7/2019 | 6/7/2019 | A | PART |
Daryl Spivey
|
|
|
We would like to schedule a partial wall rough-in in the Central Sterile at St. Luke''s Surgery Center. Josh Wilson is the site contact ###-####, please contact him in advance. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanica partial air and water...........ds
|
Pressure Test | 6/6/2019 | 6/6/2019 | 6/6/2019 | P | PART |
Daryl Spivey
|
|
|
We would like to schedule a partial rough-in/pressure test for the RO Water at St. Luke''s Surgery Center. Josh Wilson is the site contact ###-####, please contact him in advance. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical section of RO of PE pipe tested..........ds
|
Med/Gas Systems | 5/29/2019 | 5/30/2019 | 5/30/2019 | P | PART |
Daryl Spivey
|
|
|
We would like to schedule a partial med-gas rough in inspection for tomorrow afternoon at St. Luke''s. Josh Wilson is the site contact there and his number is ###-####. Please call in advance of arriving. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical partial med gas...........Area A walls ok for cover ............ds
|
Med/Gas Systems | 5/28/2019 | 5/29/2019 | 5/29/2019 | P | PART |
Daryl Spivey
|
|
|
We would like to schedule a partial med-gas rough in inspection. Josh Wilson is the site contact ###-####, please call in advance. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical start 24 hr test at 15o lb. in South section........ds
|
Other | 5/14/2019 | 5/15/2019 | 5/15/2019 | P | PART |
Daryl Spivey
|
|
|
We would like to schedule an inspection for the Above-Ground Domestic Water system at St. Luke''s Surgery Center for tomorrow afternoon. Josh Wilson is the site contact ###-####. Please call prior to arrival. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical water ok for area A............ds
|
Water and/or Sewer | 5/14/2019 | 5/15/2019 | 5/15/2019 | P | CANC |
Daryl Spivey
|
|
|
We would like to schedule an inspection for the waste and vent system at St. Luke''s Surgery Center. Josh Wilson is the contact ###-####. Please call prior to arrival. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical
|
Plumbing Rough-in | 5/15/2019 | 5/15/2019 | 5/15/2019 | P | PART |
Daryl Spivey
|
|
|
We would like to schedule an inspection for the waste and vent system at St. Luke''s Surgery Center. Josh Wilson is the contact ###-####. Please call prior to arrival. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical Area A rough in tested ok water and W/V.........ds
|
Groundwork | 4/11/2019 | 4/12/2019 | 4/12/2019 | A | PART |
Daryl Spivey
|
|
|
We would like to schedule an underground plumbing inspection for Friday morning. Site contact: Josh Wilson ###-####. Please contact before arrival. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical G/W ok in NE corner of bld...............ds
|
Pressure Test | 4/1/2019 | 4/3/2019 | 4/3/2019 | A | PART |
Daryl Spivey
|
|
|
We would like to schedule an underground pressure test inspection for Wednesday 4-3-19 in the AM. Josh Wilson is the site contact there ###-####. Please call in advance of arrival. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical partial G/W tested ok...........ds
|
Groundwork | 4/3/2019 | 4/3/2019 | 4/3/2019 | A | PASS |
Daryl Spivey
|
|
|
We would like to schedule an underground pressure test inspection for Wednesday 4-3-19 in the AM. Josh Wilson is the site contact there ###-####. Please call in advance of arrival. Thank you. Phone #: ###-#### Inspection requested via web by RM Mechanical
|
Issue PAID IN FULL permit | | | 3/26/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/25/2019 | | DONE |
|
|
|
This permit was created on the web by RM Mechanical
|